Commissioning Instructions

Before You Begin
Fume Hood Specific Sash Setup and Calibration
5 | 9
Siemens Industry, Inc.
A6V10801613
Restricted
07.06.2016
Sash Setup 2954
1.
Set REPORT to OVERVIEW.
NOTE: Numbers on the sashes show how the sash is wired. After the
physical sashes are calibrated, the position of the sashes will display in POS
SASH 1, POS SASH 2, and so on.
2.
Determine the number of horizontal sash panels. Set HZ PANEL CNT to this
value.
3.
Measure the length of the horizontal opening in inches (cm). Set TRACK
WIDTH to this value.
4.
Measure the height of the individual horizontal sash panels in inches (cm).
All the sash panels must be the same height. Set PANEL HGHT to this
value.
5.
Measure the width of the individual sash panels in inches (cm). Choose one
of the following:
If all the sash panels are the same width, set PANL WDTH 01 to this
value.
If all even horizontal track panels are one size and all odd horizontal
track panels are another size.
a.
Set PANL WDTH 01 to the width of the odd sashes.
b.
Set PANL WDTH 02 to the width of the even sashes.
If all panels are different sizes.
a.
Set PANL WDTH 01 to the width of sash 1.
b.
Set PANL WDTH 02 to the width of sash 2.
c.
Set PANL WDTH 03 to the width of sash 3.
d.
Repeat until all sashes are defined.
Example Vertical Sash Fume Hood with Fixed Area.