Operating Instructions

Product Overview
Siemens Building Technologies, Inc. 11
Figure 14. Pneumatic Damper Actuator.
Analog Output-Pneumatic (AO-P) Module
The Analog Output-Pneumatic (AO-P) Module is an electric-to-pneumatic interface between
the Fume Hood Controller and the damper actuator. The AO-P Module translates electrical
signals from the Fume Hood Controller into pneumatic signals that command the damper
actuator. The AO-P Module consists of two industrial grade air valves that supply or bleed air
to the damper actuator by using a pulse modulation technique. See Figure 15. Minimum air
supply to the AO-P Module is 18 psi and the maximum is 30 psi. The valves are rated for 24
Vac.
5.00" (127.0mm)
3.70"
(94.0mm)
SUPPLY
COMMON
EXHAUST
SUPPLY
S
(SUPPLY)
18-30 PSI
R
(ACTUATOR)
EXHAUST
FUM0240R1
Figure 15. AO-P Module.
NOTE: While the damper is being commanded, you may hear a hissing or clicking sound
coming from the AO-P module. This is due to the movement of the air valves and
the bleeding of air from the actuator. This is normal operation.