Point Database
Chapter 3 presents a description of the Fume Hood Controller point database including point
descriptors, point addresses, and a listing of applications in which each point is found.
Address Descriptor Application Description
01 CTLR ADDRESS 941, 942 Identifies the controller on the FLN trunk. Valid values: 0
through 98.
02 APPLICATION 941, 942 The identification number of the Application running in the
controller.
04 FACE VEL 941, 942 The calculated average air velocity through the face of the
fume hood.
05 LOW ALM 941, 942 This point displays an ON or OFF status. When the face
velocity goes below the value specified at LOW ALM LMT for
the time specified in ALARM TIME, the point goes into an
alarm state (ON); the red LED is illuminated, the alarm
sounds, and the message LOW Face Velocity displays at
the ODP.
06 HIGH ALM 941, 942 This point displays an ON or OFF status. When the face
velocity goes above the value specified at HI ALM LMT for the
item specified in ALARM TIME, the point goes into an alarm
state (ON); the red LED is illuminated, the alarm sounds, and
the message HIGH FACE VELOCITY displays at the ODP.
07 EMER ALM 941, 942 This point displays an ON or OFF status that indicates if the
EMERGENCY PURGE button on the ODP has been pressed.
When the operator presses the EMERGENCY PURGE button,
the point is ON, the red LED is illuminated, the alarm sounds,
and EEE and EMERGENCY MODE display at the ODP. If
pressed again, then the point is OFF. This point can be
commanded by a field panel.
08 GEN FAILURE 941, 942 Indicates a hardware failure (e.g., the sash sensor) with an ON
or OFF status. The red LED is illuminated; the alarm sounds,
and FFF and GENERAL FAILURE display at the ODP.
09 FVEL STPT 941, 942 The face velocity setpoint in feet per minute (m/s) that is
maintained by the Fume Hood Controller. Valid values: 0
through 225 ft/min (0-1.2954 m/s).
10 HI ALM LMT 941, 942 The value above FVEL STPT, in percent, at which the red LED
and audible alarm are activated on the ODP. This point is the
setpoint for HIGH ALM. Valid values: 100 through 255%.