Application
Sequence of Operation
Fail Mode Operation
37
Siemens Industry, Inc.
BACnet LCM-OAVS, Application 6754
140-1325
2015-07-07
If AVS FAILMODE equals 7, the supply Damper will hold. The general exhaust Venturi
Air Valve will also hold if a fume hood is present (that is, if MAX HOOD VOL > 0). If a
fume hood is absent, then the general exhaust Venturi Air Valve will close if the room
is being positively pressurized and open if the room is neutral or negatively pressurized
(that is if VOL DIF STPT is equal to or greater than 0).
If AVS FAILMODE equals
8, the supply Damper will open if the room is being positively
pressurized and close if the room is neutral or negatively pressurized. The general
exhaust Venturi Air Valvewill hold if a fume hood is present. If a fume hood is absent,
the general exhaust Venturi Air Valve will close if the room is being positively
pressurized and open if the room is neutral or negatively pressurized.
NOTE:
If AVS FAILMODE is set greater than 8, it will default to 0.
Fail Mode Operation
If one of the controller’s accessories (inputs) fails, a failure mode sequence is initiated
that leads to the failure of VOL DIFFRNC. The following figure shows the order in
which points will fail.
* If MAX HOOD VOL is set to 0, a “Failed” status of HOOD VOL will not initiate a failure
in TOTL EXHAUST or VOL DIFFRNC. See
Fume Hood Flow Input
.
Air Velocity Sensors – If one or both of the LCM air sensor signals (SUP AIR VOL,
GEX AIR VOL) are out of range (for example, improper wiring to/from the Offboard Air
Module(s), tubing not connected or connected backward), then the actions of the
supply and general exhaust Venturi Air Valves will depend on the value of AVS
FAILMODE. Once GEX AIR VOL and SUP AIR VOL are normal, the supply and
general exhaust Venturi Air Valves return to normal operation.
See
Operation of AVS FAILMODE
for more information.