Application
Point Database Application 6754
46
Siemens Industry, Inc.
BACnet LCM-OAVS, Application 6754
140-1325
2015-07-07
Object Type
Object
Instance
(Point
Number)
Object Name (Descriptor)
Factory
Default (SI
Units)
Eng Units
(SI Units)
Range
Active Text
Inactive
Text
AO
105
VENTURI ACT
1
--
0-255
--
--
AO
106
MODHTG FLO
300 (1.524)
FPM (MPS)
0-4095
--
--
AO
107
DO DIR.REV
0
--
0-255
--
--
AI
{108}
RM RH
50
PCT
0-102
--
--
AO
109
FAIL TIME
60
SEC
0-510
--
--
AO
110
MTR SETUP
0
--
0-255
--
--
AO
{111}
SUP DMP POS
0
PCT
0-102
--
--
AO
112
MTR1 TIMING
95
SEC
0-511
--
--
AO
113
MTR1 ROT ANG
90
--
0-255
--
--
AO
117
MINHOODVOLTS
1
VOLTS
0-10.23
--
--
AI
{118}
RM CO2
1000
PPM
0-8191
--
--
AO
{119}
TABLE VOLTS
0
VOLTS
0-10.23
--
--
AO
{120}
V TABLE PT
0
--
0-255
--
--
AO
121
HI LIMIT
1
--
0-2.55
--
--
AO
122
LO LIMIT
1
--
0-2.55
--
--
BO
124
G OPEN LOOP
NO
--
Binary
YES
NO
AO
125
SUP MAX RATE
0 (0.0)
FPM (MPS)
0-4095
--
--
AO
126
GEX MAX RATE
0 (0.0)
FPM (MPS)
0-4095
--
--
BO
{127}
PPCL STATE
EMPTY
--
Binary
LOADED
EMPTY
1)
Object Types are; Analog Input (AI), Analog Output (AO), Binary Input (BI) and Binary Output (BO).
2)
A single value in a column means that the value is the same in English units and in SI units.
3)
Point numbers that appear in brackets { } may be unbundled at the field panel.