Basic Documentation

Technology Report
June, 2003
Siemens Industry, Inc. Page 1 of 10
Laboratory Ventilation Systems
Getting the Best Bang for the Buck
This report focuses on what type of ventilation
system can yield the most favorable life cycle cost
for a chemical laboratory with fume hoods. In many
situations it's not possible to provide a one size fits
all answer because of the many individual variables
involved. Laboratory activities extend from basic
chemistry instruction in teaching labs to advanced
research. Laboratory rooms vary in size and involve
an endless array of furnishings and equipment. All of
these factors impact the type of ventilation system
that will be most appropriate, as well as result in the
lowest life cycle cost. This report is intended as a
guide to selecting the type of ventilation system that
is likely to attain the lowest life cycle cost for a
specific type of laboratory and thus get the best
bang for the buck.
Ventilation System Characteristics
Laboratory ventilation standards require that a
laboratory's ventilation system must remain
functioning at all times when there are hazardous
chemicals within the room or a fume hood. Under
these situations, the laboratory room's ventilation
system may only be fully shut down for short periods
when necessary for testing, adjusting and servicing.
At all other times some amount of ventilation airflow
must be maintained. Thus, energy consumption
becomes a significant expenditure. Figure 1 shows
the relative e
nergy consumption characteristics of
the commonly applied types of laboratory ventilation
systems during the room's occupied and unoccupied
periods. An overview of each type of ventilation
system follows. See Table 1 for the recommended
ventilation sy
stem for various chemistry laboratory
applications.
Constant Air Volume (CAV) 1-
Position
A CAV 1-Position ventilation system provides a
constant ventilation airflow through a laboratory
room and its fume hoods during both the occupied
and unoccupied periods—24 hours a day and 7
days a week. It is the simplest system to design and
requires a limited amount of associated airflow
controls. It also requires a minimum amount of
knowledge and oversight by support (maintenance)
personnel. However, the tradeoff for this simplicity is
high-energy consumption since there is no provision
for reducing ventilation airflow during times when the
room is unoccupied or the fume hoods are not being
used. However, in certain limited applications, the
CAV 1-Position ventilation system can be the
optimum type of system.
Constant Air Volume (CAV) 2-
Position
A CAV 2-Position ventilation system provides two
levels of ventilation airflow through the laboratory
room and its fume hoods. It provides a higher
ventilation airflow rate when the laboratory room is
occupied and a lower amount when the room is
unoccupied. As with the basic CAV 1-Position
system, it is not a very complex design and requires
only a modest amount of associated airflow controls.
It requires some supervision and knowledge by
support personnel, and is often the optimum type of
ventilation system for certain types of laboratories.
Document No. 1
49- 980

Summary of content (10 pages)