Application
Sequence of Operation
Ventilation – Constant Volume Mode
15
Siemens Industry, Inc.
Application Note, App 6751
140-1331
2015-07-07
Ventilation – Constant Volume Mode
During Constant Volume (CV) operation, the active supply airflow minimum is used to
ensure that the room always receives enough supply air for proper ventilation. If
necessary, the application raises the general exhaust flow to keep the supply flow from
dropping below the minimum. See
Calculating Exhaust Flow Setpoint
for more
information.
In CV mode the active supply minimum is the setpoint. The active supply airflow
minimum is used to ensure that the room always receives enough supply air for proper
ventilation.
During CV operation, the air volume out of the supply box will equal the active supply
airflow minimum as long as this is sufficient to maintain proper room pressurization.
NOTE:
Regardless of the operation—VAV or CV temperature control—airflow out of both the
supply and general exhaust box will vary as needed in order to maintain proper room
pressurization whenever HOOD VOL changes.
AVS Calibration
Calibration of the air velocity transducer(s) is periodically required to maintain accurate
air velocity readings. Depending on the value of CAL SETUP, calibration takes place
either at fixed time intervals or whenever the application goes into unoccupied mode.
When calibration is in progress, CAL AIR equals YES. After calibration, CAL AIR
returns to NO.
The application uses Autozero Modules connected to AUTOZERO DO8. This means
that the supply and general exhaust flow control devices do not close during calibration
of the transducers.
NOTE:
The LCM does not monitor Fume Hood flow changes for 3 seconds during AVS
calibration.
Airflow Control
Supply flow and general exhaust are controlled by feedback loops that operate control
dampers so that the measured flows maintain their setpoints. The feedback gains SUP
P GAIN and GEX P GAIN are adjustable.
The damper command points (SUP DMPR CMD and GEX DMPR CMD) indicate the
rate at which the dampers move. The points do not indicate damper position. A value
of:
100% indicates that the damper is being opened as quickly as possible
10% indicates that the damper is being opened slowly
0% indicates that the damper does not move at all
A negative number indicates that the damper is closing at a corresponding rate; for
example, a value of -100% means the damper is closing at full speed