Application

Point Database Application 6751
30
Siemens Industry, Inc.
Application Note, App 6751
Point Database Application 6751
Object Type
Object
Instance
(Point
Number)
Object Name (Descriptor)
Factory
Default (SI
Units)
Eng Units
(SI Units)
Range
Active Text
Inactive
Text
AO
1
CTLR ADDRESS
255
--
0-255
--
--
AO
2
APPLICATION
6792
--
0-32767
--
--
AO
3
TEMP OFFSET
0.0 (0.0)
DEG F
(DEG C)
-31.75-32
--
--
AI
{04}
ROOM TEMP
74.0
(23.44888)
DEG F
(DEG C)
48-111.75
--
--
AO
5
OCC DIF STPT
400
(188.7599)
CFM (LPS)
-8000-8380
--
--
AO
6
UOC DIF STPT
400
(188.7599)
CFM (LPS)
-8000-8380
--
--
AO
7
RM STPT MIN
55.0
(12.80888)
DEG F
(DEG C)
48-111.75
--
--
AO
8
RM STPT MAX
90.0
(32.40888)
DEG F
(DEG C)
48-111.75
--
--
AO
{09}
TEMP CTL VOL
0 (0.0)
CFM (LPS)
0-32764
--
--
BO
10
GEX DMPR DIR
NOPEN
--
Binary
NCLOSE
NOPEN
BO
11
SUP DMPR DIR
NCLOSE
--
Binary
NCLOSE
NOPEN
AO
12
OCC ENA
0
--
0-255
--
--
AI
{13}
ROOM STPT
74.0
(23.44888)
DEG F
(DEG C)
48-111.75
--
--
AI
{14}
AI 4
0
PCT
0-102.3
--
--
AI
{15}
HOOD SIG AI3
0
VOLTS
0-10.23
--
--
AO
16
VENT ALM DEL
30
SEC
0-255
--
--
AO
17
ALARM ENA
0
--
0-255
--
--
AO
18
START
50
PCT
0-102
--
--
BI
{19}
OCC BUTTON
OFF
--
Binary
ON
OFF
BO
{21}
OCC.UNOCC
OCC
--
Binary
UNOCC
OCC
BO
{22}
VOL DIF ALM
OFF
--
Binary
ON
OFF
BO
{23}
NET ALM CMD
OFF
--
Binary
ON
OFF
BI
{24}
OCC SWIT DI2
OFF
--
Binary
ON
OFF
BO
{25}
BUTTON CMD
OCC
--
Binary
UNOCC
OCC
AO
26
GEX P GAIN
0.04
--
0-4.095
--
--
BI
{27}
ALM SWIT DI6
OFF
--
Binary
ON
OFF
AO
28
TRACK MODE
0
--
0-255
--
--
BO
{29}
NET OCC CMD
OCC
--
Binary
UNOCC
OCC