Application

Point Database Application 6751
33
Siemens Industry, Inc.
Application Note, App 6751
Object Type
Object
Instance
(Point
Number)
Object Name (Descriptor)
Factory
Default (SI
Units)
Eng Units
(SI Units)
Range
Active Text
Inactive
Text
AO
106
MODHTG FLO
300 (1.524)
FPM (MPS)
0-4095
--
--
AO
107
DO DIR.REV
0
--
0-255
--
--
AI
{108}
RM RH
50
PCT
0-102
--
--
AO
117
MINHOODVOLTS
1
VOLTS
0-10.23
--
--
AI
{118}
RM CO2
1000
PPM
0-8191
--
--
BO
{127}
PPCL STATE
EMPTY
--
Binary
LOADED
EMPTY
1)
Object Types are; Analog Input (AI), Analog Output (AO), Binary Input (BI) and Binary Output (BO).
2)
A single value in a column means that the value is the same in English units and in SI units.
3)
Point numbers that appear in brackets { } may be unbundled at the field panel.