Auto Discovery
Auto Discovery allows you to automatically discover and identify PTEC/ATEC
controllers on the BACnet MS/TP Network. There are two basic configurations:
Devices not configured with an address. (Devices are discovered by their unique
serial number.)
Devices configured with an address and available for modification.
Auto Addressing
Auto Addressing allows you to automatically assign device addresses to a
PTEC/ATEC controller on the BACnet MS/TP Network. If a controller is not configured
with a MAC address, you have the option to auto-address or manually address the
controller. During this time the baud rate is automatically detected by the controller.
Controller(s) must be connected on the BACnet/IP network in order for automatic
addressing to occur.
Hardware Inputs
Analog
Air velocity sensor (s) – (one or two depending on setup)
Fume hood controller input or FFM
Room temperature sensor
Digital
Occupancy button (option on room temperature sensor)
(Optional)
Occupancy switch
(Optional)
Alarm switch
Hardware Outputs
Analog
Reheat valve
Digital
Autozero Solenoid in Offboard Air Module (DO 8)
(Optional)
Alarm
Supply damper (two DOs)
General exhaust damper (two DOs)
Ordering Notes
570-803PA
BACnet LCM-OAVS VAV Room Pressurization Controller with HW Reheat
and Fast-acting Damper Actuation — One Exhaust, One Supply
Requires Offboard Air Module(s) – order and ship separately
550-819B
Offboard Air Module (OAM) – order and ship separately
GNP191.1P