Application
Point Database Application 6750
42
Siemens Industry, Inc.
Application Note, App 6750
140-1328
2015-07-07
Point Database Application 6750
Object
Type
Object
Instance
(Point
Number)
Object Name
(Descriptor)
Factory
Default
(SI Units)
Eng Units
(SI Units)
Range
Active
Text
Inactive
Text
AO
1
CTLR ADDRESS
255
--
0-255
--
--
AO
2
APPLICATION
6792
--
0-32767
--
--
AO
3
TEMP OFFSET
0.0 (0.0)
DEG F
(DEG C)
-31.75-32
--
--
AI
{04}
ROOM TEMP
74.0
(23.44888)
DEG F
(DEG C)
48-111.75
--
--
AO
5
OCC DIF STPT
400
(188.7599)
CFM
(LPS)
-8000-8380
--
--
AO
6
UOC DIF STPT
400
(188.7599)
CFM
(LPS)
-8000-8380
--
--
AO
7
RM STPT MIN
55.0
(12.80888)
DEG F
(DEG C)
48-111.75
--
--
AO
8
RM STPT MAX
90.0
(32.40888)
DEG F
(DEG C)
48-111.75
--
--
AO
{09}
TEMP CTL VOL
0 (0.0)
CFM
(LPS)
0-32764
--
--
AO
{10}
TABLE FLOW
0 (0.0)
CFM
(LPS)
0-32764
--
--
BO
11
SUP VLV STAT
NOTCAL
--
Binary
NOTCAL
CAL OK
AO
12
OCC ENA
0
--
0-255
--
--
AI
{13}
ROOM STPT
74.0
(23.44888)
DEG F
(DEG C)
48-111.75
--
--
AI
{14}
AI 4
0
PCT
0-102.3
--
--
AI
{15}
HOOD SIG AI3
0
VOLTS
0-10.23
--
--
AO
16
VENT ALM DEL
30
SEC
0-255
--
--
AO
17
ALARM ENA
0
--
0-255
--
--
AO
18
START
50
PCT
0-102
--
--
BI
{19}
OCC BUTTON
OFF
--
Binary
ON
OFF
BO
{21}
OCC.UNOCC
OCC
--
Binary
UNOCC
OCC
BO
{22}
VOL DIF ALM
OFF
--
Binary
ON
OFF
BO
{23}
NET ALM CMD
OFF
--
Binary
ON
OFF
BI
{24}
OCC SWIT DI2
OFF
--
Binary
ON
OFF
BO
{25}
BUTTON CMD
OCC
--
Binary
UNOCC
OCC
AO
26
GEX P GAIN
0.015
--
0-4.095
--
--
BI
{27}
ALM SWIT DI6
OFF
--
Binary
ON
OFF
AO
28
TRACK MODE
0
--
0-255
--
--