Data Sheet for Product

3
Siemens Industry, Inc.
A6V10801251
07.06.2016
53” Vertical UniTrak Sash Kit 546-00485
71” Vertical UniTrak Sash Kit 546-00484
85” Vertical UniTrak Sash Kit 546-00443
34” Horizontal Sash Kit 546-00495
43” Horizontal Sash Kit 546-00493
52” Horizontal Sash Kit 546-00492
70” Horizontal Sash Kit 546-00491
84” Horizontal Sash Kit 546-00442
Product documentation
Topic Title Document ID:
Installation, sash wiring Fume Hood Sash Open Area Module (SOAM)
Installation Instructions
A6V10801244
Installation, sash wiring Retracting Cable Sash Sensor 570-112
Installation, sash wiring UniTrak Sensor Assembly Kit 546-00449
Technical Spec, FH Controller PTEC FHC cut sheet 149-857
Technical Spec, Lab Room
Controller
PTEC LCM cut sheet 149-855
Related documents such as environmental declarations, CE declarations, etc., can be
downloaded at the following Internet address:
http://siemens.com/bt/download
Technical data
Power supply
Power supply
Operating voltage AC 24 V (± 20%)
Frequency 50/60 Hz.
Power consumption including connected field devices Max. 5 VA
Inputs
NOTE:
Do not apply power to the resistive inputs, the controller will not work properly.
Voltage measurement, analog
Type Range Resolution Accuracy
AI 0...10 V 0...11 V 2 mV ± 0.1 V
Open circuit: Negative voltage -1.5 V, 8 μA (line failure detection)
Resistive measurement, analog
Type Range Resolution Relative Accuracy
AI 720 k 0...720 k 0.25 inch ± 0.25 inch
Failure detection for open circuits