Outputs
Analog outputs
AO 0 to 10 V
Interfaces
Interfaces
USB (2.0) Plug: Type B.
Data rate: 1.5 Mbps and 12 Mbps.
Galvanic isolation to ground. No isolation from I/O ground.
Sensor Bus Digital communication to DXR Lab Controller
Wiring connections
Wiring connections
Pluggable screw terminals Copper wire or copper strands with ferrules
1 x 0.6 mm (0.02 in) dia. to 2.5 mm
2
(0.004 in
2
) or
2 x 0.6 mm (0.02 in) dia. to 1 mm
2
(0.0015 in
2
).
Copper strands without ferrules
1 x 0.6 mm (0.02 in) dia. to 2.5 mm
2
(0.004 in
2
) or
2 x 0.6 mm (0.02 in) dia. to 1.5 mm
2
(0.002 in
2
).
Slotted screws Size 1, tightening torque 0.6 Nm (0.44 lb-ft).
Wiring lengths for signals. Signal lines 80 m (263 ft).
Ambient conditions and protection classification
Climatic ambient conditions
Transport (packaged for transport) as per
EN 60721-3-2
Operation as per EN 60721-3-3.
Class 2K3
Temperature -25...70 °C (-13... 158 °F)
Air humidity 5...95%.
Class 3K5
Temperature -5...50 °C (23... 122 °F)
Air humidity 5...95%.
Standards, directives and approvals
EU conformity (CE) EN61000-6-3/EN61000-6-2
RCM conformity AS/NZS 61000-6-3
UL Certification UL916
cUL and CSA Certification CSA C22.2 No. 205
Federal Communications Commission FCC CFR 47 Part 15 Class B.
Disposal
The device is considered electrical and electronic equipment for disposal in terms of the
applicable European Directive and may not be disposed of as domestic garbage.
Dispose of the device through channels provided for this purpose.