Data Sheet for Product

Page 4 of 10
Siemens Industry, Inc
Table 1. Minimum Pressure Drop @ Listed Airflows.
Terminal
Airflow
Min SP
Terminal
Airflow
Min SP
Terminal
Airflow
Min SP
Size
CFM
In. W.G.
Size
CFM
In. W.G.
Size
CFM
In. W.G.
4
0.75
0.11
7
150 0.05
12
350 0.02
150
0.42 300 0.18 850 0.12
225 .95 450 0.41 1350 0.29
280 1.47 600
0.73 1850 0.55
5
100 0.07 750 1.15 2350 0.89
200 0.27 855 1.49 2515 1.01
300 0.61
8
175 0.03
14
500 0.03
400 1.08 375
0.14 1250 0.18
435 1.28 575
0.32 2000 0.47
6
125 0.07 775 0.59 2750 0.89
250 0.27 975 0.93 3420 1.38
375 0.61 1115 1.22
500 1.09
10
250 0.02
16
600 0.03
630 1.72
550 0.11 1400 0.15
850 0.27 2200 0.38
1150 0.49 3000 0.71
1450 0.78 3800 1.13
1745 1.13 4470 1.57
Performance Notes:
1. Tested in accordance with ASHRAE Standard 139-1996: “Methods of Testing for Rating Ducted Air Terminal Units.”
2. Min SP is minimum static pressure measured across terminal in inches water gauge.