Data Sheet for Product
Table Of Contents
Page 4 of 10
Siemens Industry, Inc
Table 1. Minimum Pressure Drop @ Listed Airflows.
Terminal
Airflow
Min SP
Terminal
Airflow
Min SP
Terminal
Airflow
Min SP
Size
CFM
In. W.G.
Size
CFM
In. W.G.
Size
CFM
In. W.G.
4
0.75
0.11
7
150 0.05
12
350 0.02
150
0.42 300 0.18 850 0.12
225 .95 450 0.41 1350 0.29
280 1.47 600
0.73 1850 0.55
5
100 0.07 750 1.15 2350 0.89
200 0.27 855 1.49 2515 1.01
300 0.61
8
175 0.03
14
500 0.03
400 1.08 375
0.14 1250 0.18
435 1.28 575
0.32 2000 0.47
6
125 0.07 775 0.59 2750 0.89
250 0.27 975 0.93 3420 1.38
375 0.61 1115 1.22
— —
500 1.09
10
250 0.02
16
600 0.03
630 1.72
550 0.11 1400 0.15
— —
850 0.27 2200 0.38
— —
1150 0.49 3000 0.71
— —
1450 0.78 3800 1.13
— —
1745 1.13 4470 1.57
Performance Notes:
1. Tested in accordance with ASHRAE Standard 139-1996: “Methods of Testing for Rating Ducted Air Terminal Units.”
2. Min SP is minimum static pressure measured across terminal in inches water gauge.