Data Sheet for Product

Table Of Contents
Siemens Industry, Inc. Page 3 of 4
Fume Hood Controller
Specifications
Dimensions 4-1/8" W × 11-1/4" L × 1-1/2" H
(105 mm × 197 mm ×38 mm)
Weight Approx. 3 lbs (1.35 kg)
Power Requirements
Operating Range 19.2 to 27.6 Vac 50 or 60 Hz
Power Consumption 8 VA (Nominal) to 12 VA (Peak) @ 24
Vac (plus 12 VA per DO)
Inputs
Analog 1 Vertical sash sensor
(10K thermistor)
1 Spare AI
(0-10 Vdc/4-20 mA)
1 External face area or Flow sensor
(0-10 Vdc/4-20 mA)
2 air velocity sensor inputs
(Only for OAM inputs)
Digital 2 dry contacts
Outputs
Analog (3) 0 to 10 Vdc
Digital (8) DO 24 Vac optically isolated solid
state switches @ 0.5 amp
(1) DO dedicated to AZ function
Communications
Remote 4800 bps FLN Trunk
Local WCIS
Control Performance
Speed of Response <1 second to flow change
Ambient Conditions
Shipping and Storage
Temperature
-13°F to 158°F (-25°C to 70°C)
Operating Temperature 32°F to 122°F (0°C to 50°C)
Humidity Range 5% to 95% rh (non-condensing)
Airflow Sensing and Control
OAM
Measurement Range
Accuracy
0 to 5600 fpm (0 to 26 m/s) 3.5%
reading maximum error from velocity
pressure of
0.02”WC(5 Pa) to 2.0% error at
maximum velocity.
(Optional)
Differential
Pressure Input
Measurement Range
Accuracy
0 to 2.5" WC
± 0.4 % FS
Speed of Response <1 second to flow change
Agency Listings
UL Listing UL 916, PAZX
cUL Listed Canadian Standards C22.2 No. 205-
M1983, PAZX7
FCC Compliance FCC Part 15, Class A
Operator Display Panel
The Operator Display Panel (ODP) includes a custom
designed package for visual and audible indication of
fume hood operating conditions and push-buttons for
emergency mode operation, alarm silence and user-
defined auxiliary functions. The panel is mounted on
the fume hood in an easy-to-access location and will
fit over an unused hood electrical box or over pre-
drilled holes. RJ-11 type connectors provide
termination to the Fume Hood Controller and for the
Portable Operator’s Terminal. One Operator Display
Panel is supported per Fume Hood Controller.
The Operator Display Panel supports the following
functions:
l Digital display of face velocity in FPM (MPS)
l Green, yellow and red status lights
l Emergency purge push button
l Alarm horn with silence push button
l Auxiliary push buttons for more information
l Animated Graphics to encourage users to close
sashes when not using the hood
The face velocity display also indicates high and low
alarm conditions, emergency purge activation, and
diagnostic failure mode conditions when the controller
is in the minimum flow mode. Face velocity FPM
(MPS) display may be blanked as an option for
applications where the user does not desire the face
velocity reading.