Application
Sequence of Operation
Ventilation – VAV Mode
16
Siemens Industry, Inc.
Application Note, App 6752
140-1322
2015-07-07
Ventilation – VAV Mode
During VAV operation, the ventilation works as follows:
OCC SUP MIN, the occupied supply minimum, is used to ensure that the room
receives enough supply air for proper ventilation during the occupied mode. UOC SUP
MIN is used to ensure that the room receives enough supply air for proper ventilation
during the unoccupied mode. If necessary, the application raises the general exhaust
flow to keep the supply flow from dropping below the minimum. See
Calculating
Exhaust Flow Setpoint
for more information.
NOTE:
Since Application 6752 places a higher priority on pressurization than it does on
ventilation, the currently active supply minimum (OCC SUP MIN or UNOCC SUP
MIN) may be overridden to maintain negative pressurization.
Ventilation Setback in VAV Mode
Ventilation setback allows the minimum and maximum flows (air change rate) for each
VAV terminal to vary based on occupancy mode (OCC.UNOCC). This allows several
options for reducing the ventilation for unoccupied periods, including:
Lowering the minimum supply flow, which allows a lower air change rate, but
maintains cooling control.
Lowering the maximum flow, which limits the air change rate and reduces cooling
capacity.
Closing the general exhaust, which lowers airflow and disables cooling completely.
Ventilation – Constant Volume Mode
During Constant Volume (CV) operation, the active supply airflow minimum is used to
ensure that the room always receives enough supply air for proper ventilation. If
necessary, the application raises the general exhaust flow to keep the supply flow from
dropping below the minimum. See
Calculating Exhaust Flow Setpoint
for more
information.
In CV mode the active supply minimum is the setpoint. The active supply airflow
minimum is used to ensure that the room always receives enough supply air for proper
ventilation.
During CV operation, the air volume out of the supply box will equal the active supply
airflow minimum as long as this is sufficient to maintain proper room pressurization.
NOTE:
Regardless of the operation—VAV or CV temperature control—airflow out of both the
supply and general exhaust box will vary as needed in order to maintain proper room
pressurization whenever HOOD VOL changes.