AI
{30}
GEX AIR VOL
0 (0.0)
CFM (LPS)
0-32764
--
--
AO
{31}
OCC SUP MAX
3400
(1604.46)
CFM (LPS)
0-32764
--
--
AO
{32}
OCC SUP MIN
340
(160.446)
CFM (LPS)
0-32764
--
--
AO
{33}
OCC GEX MAX
1100
(519.09)
CFM (LPS)
0-32764
--
--
AO
{34}
OCC GEX MIN
600
(283.14)
CFM (LPS)
0-32764
--
--
AI
{35}
SUP AIR VOL
0 (0.0)
CFM (LPS)
0-32764
--
--
AO
36
SUP FLO COEF
0.73
--
0-2.55
--
--
AO
{37}
REHEAT AO1
0
VOLTS
0-10.23
--
--
AO
38
DIF ALM DBD
100 (47.19)
CFM (LPS)
0-4092
--
--
AO
39
DIF ALM DEL
30
SEC
0-255
--
--
AO
40
AVS FAILMODE
0
--
0-255
--
--
BO
{41}
DO 1
OFF
--
Binary
ON
OFF
BO
{42}
DO 2
OFF
--
Binary
ON
OFF
BO
{43}
DO 3
OFF
--
Binary
ON
OFF
BO
{44}
DO 4
OFF
--
Binary
ON
OFF
BO
45
TRACK METHOD
FLOW
--
Binary
FLOW
STPT
BO
{46}
DO 5
OFF
--
Binary
ON
OFF
BO
{47}
ALARM DO7
OFF
--
Binary
ON
OFF
BO
{48}
AUTOZERO DO8
OFF
--
Binary
ON
OFF
AO
{49}
VALVE CMD
0
PCT
0-102
--
--
BO
50
GEX VLV STAT
NOTCAL
--
Binary
NOTCAL
CAL OK
AO
52
MAX HOOD VOL
0 (0.0)
CFM (LPS)
0-32764
--
--
AI
{53}
TOTL EXHAUST
0 (0.0)
CFM (LPS)
0-32764
--
--
AO
54
GEX FLO COEF
0.73
--
0-2.55
--
--
AO
{55}
SUP DMPR AO2
0
VOLTS
0-10.23
--
--
AO
{56}
GEX DMPR AO3
0
VOLTS
0-10.23
--
--
AO
57
VALVE CLOSED
10
VOLTS
0-10.23
--
--
AO
58
VALVE OPEN
0
VOLTS
0-10.23
--
--
AO
60
GEXDUCT AREA
1.0
(0.09292)
SQ. FT (SQ
M)
0-6.375
--
--
AO
{61}
OTHER SUP
0 (0.0)
CFM (LPS)
0-16380
--
--
BO
{62}
CAL SUP VLV
NO
--
Binary
YES
NO
AO
65
ROOM P GAIN
20.0 (36.0)
--
0-8191.75
--
--
AO
66
ROOM I GAIN
0.01 (0.018)
--
0-32.767
--
--