Object Type
Object
Instance
(Point
Number)
Object Name (Descriptor)
Factory
Default (SI
Units)
Eng Units
(SI Units)
Range
Active Text
Inactive
Text
AI
{84}
AI 5
74.0
(23.496)
DEG F
(DEG C)
37.5-165
--
--
BO
{94}
CAL AIR
NO
--
Binary
YES
NO
AO
95
CAL SETUP
4
--
0-255
--
--
AO
96
CAL TIMER
12
HRS
0-255
--
--
AO
97
DUCT AREA 1
1.0
(0.09292)
SQ. FT
(SQ M)
0-6.375
--
--
AO
{99}
ERROR STATUS
0
--
0-255
--
--
AO
104
SENSOR SEL
0
--
0-255
--
--
AO
107
DO DIR.REV
0
--
0-255
--
--
AI
{108}
RM RH
50
PCT
0-102
--
--
AI
{118}
RM CO2
1000
PPM
0-8191
--
--
BO
{127}
PPCL STATE
EMPTY
--
Binary
LOADED
EMPTY
1)
Object Types are; Analog Input (AI), Analog Output (AO), Binary Input (BI) and Binary Output (BO).
2)
A single value in a column means that the value is the same in English units and in SI units.
3)
Point numbers that appear in brackets { } may be unbundled at the field panel.