Specifications
Dimensions .......................... 3.08”W x 7.42”H x 1.5”D
(78.23 mm x 188.47 mm x 38.1 mm)
Power Requirements
Operating Range...............................24 Vac 50/60 Hz
Power Consumption........................... 2.5 Va (class 2)
@ 24 Vac
Ambient Conditions
Storage Temperature...........................-40°F to 167°F
(-40°C to 75°C)
Operating Temperature ........................32°F to 120°F
(0°C to 49°C)
Humidity Range .............20 to 93% (non-condensing)
Display
Size ........................................................... 3 digit LCD
Range ................................................. 50 to 250 FPM
(0.25 m/s to 1.25 m/s)
Resolution..................................... 1 FPM (adjustable)
(0.005 m/s)
Update Rate ................................................ 1 second
LEDs .............................................................2 - 1 green
1 red
Alarms .....................................................1 audio buzzer
(85 dB @ 10 cm, 2.3 KHz resonance)
1 red LED
Signal to central terminal via
APOGEE FLN
Remote Alarm Output ............ 24 Vac (12 Va) Class 2
Auxiliary Digital Input ...............................Dry Contact
Face Velocity Sensor
Accuracy ..................................... ±10 FPM (0.05 m/s)
Agency Listings
UL Listing
for Smoke Control ...............................UL 864, UUKL
UL Listing
for Energy Management...................... UL 916, PAZX
UL Listing
for Signal System Unit......................... UL 864, UDTZ
UL Listing
for Process
Management Equipment.................... UL 916, QUAY
ULC Listed ........................................... UL/ORD-C100
Ordering Information
Description Part Numbers
Fume Hood Monitor 546-00303a
Mounting Kit 546-00303b
Fume Hood Monitor User’s Card 125-1990
Fume Hood Monitor Owner’s
Manual
125-1991
Fume Hood Evaluation Kit 546-00320