Data Sheet for Product

Page 4 of 5 Siemens Building Technologies, Inc.
Laboratory Controller Module
Laboratory Controller ModuleLaboratory Controller Module
Laboratory Controller Module-
--
- Electronic
Electronic Electronic
Electronic
The Laboratory Controller Module includes a
microprocessor-based assembly with on-board
differential pressure transducers for airflow
measurement. Wiring termination for input and output
points, FLN communications, and power are provided
via removable terminal block connections. The room
temperature sensor is connected to an on board RJ-11
jack.
The controller connects to the following external
devices:
Fume Hood Controller
Fume Hood Flow Module
Lab Electronic Damper Actuator Assemblies
Electronic Hot Water Valve
Room Temperature Sensor
Portable Operators Terminal
APOGEE Automation System
Digital Input Devices (e.g., wall switches)
Digital Output Devices (e.g., alarm horn)
Laboratory Room Air Terminals boxes
Controller Specifications
Power Requirements
Operating Range
Power Consumption:
19 to 28 VAC 50 or 60 Hz
3.9 VA (Nominal) to
5.3 VA (Peak) @ 24 VAC
(plus loads)
Inputs
Analog
Room Temperature
Supply Airflow
Exhaust or 2
nd
supply
Airflow
Fume Hood Exhaust
Flow
Digital
Occupied Switch
(optional)
Alarm Switch (optional)
1 temperature sensor
1 air velocity sensor
1 air velocity sensor
1 (0 -10) Vdc flow signal
1 DI
1 DI
Outputs
Digital
Auto-zero
Pressure Alarm
(optional)
Room Occupied Status
(optional)
Supply Airflow Control
General Exhaust or 2
nd
Supply Airflow Control
Spare
1 DO
1 DO
1 DO
1 floating – 2 DOs
1 floating – 2 DOs
1 DO
Note: All Digital Output (DO) points are 24 VAC optically isolated solid
state switch @ 0.5A.
Analog
Temperature Control
0 - 10V
Dimensions
Enclosure
Weight
13.5"W x 14.5"L x 4"D
(320 mm x 340 mm x 102 mm)
Approx. 10 lbs (4 kg)
Control Performance
Controlled Temperature
Flow Control Speed of
Response
±
1.0
°
F (0.6
°
C)
Accuracy, Heating or Cooling
1.5 sec.
Environmental Conditions
Storage Temperature
Operating Temperature
Humidity Range
-40
°
F to 167
°
F (-40
°
C to 75
°
C)
32
°
F to 104
°
F (0
°
C to 40
°
C)
10 to 95% (non-condensing)
Agency Listings
FCC
UL
Class B, subpart J
916 PA ZX 864-UDTZ
Communications
Remote
Local
FLN Trunk
Portable Operator’s Terminal
Laboratory Room Controller Flow
Measurement
Laboratory Room Controller airflow measurement
consists of the controller module A/D conversion
circuitry, on-board differential pressure transducers (2)
and auto-zero modules (2). Air velocity sensors (within
the air terminal) send the velocity signal to the LRC
differential pressure transmitter. Auto-zero modules
are connected to the air velocity pressure transducer's
inlet ports to enable automatic periodic re-calibration.
This re-calibration ensures accurate, drift-free and
stable airflow measurement. Automatic re-calibration
of the differential pressure transducers occurs upon
system power-up and when airflows are stable.