Notes
Security
CAUTION
National safety regulations
Failure to comply with national safety regulations may result in personal injury and property
damage.
Observe national provisions and comply with the appropriate safety regulations.
Safety notes
Use the cable sensor as described and follow the listed precautionary measures.
Opening the sensor housing damages the sensor.
Do not allow the cable to snap back to the sensor.
Only connect the sensor to the predefined terminals on the Siemens controller.
Attach the sensor to the sensing object when the cable is wound up.
Do not unwind the cable past the sensing range.
Do not damage the cable.
Do not oil or grease the cable.
Do not bend the cable.
Do not deflect the cable.
Do not allow the cable to drag on objects.
Installation
General
Mount the sensor using three M3 screws or using the supplied mounting bracket. The device
can be mounted without special sensor orientation.
Make sure that the mounting location does not result in a soiled or damaged sensing cable.
Measure sash opening
Measure the length from the mounting surface to the sash. Confirm that sensor extension
length is sufficient for installation.
Mark the location of the sash bottom with the sash fully open and closed.
Measure the distance between fully open and closed position of the sash. Add 5 cm (2 in) to
account for over-travel.
Bracket mounting on sensor
To change measuring cable direction, remove the bracket attaching screws and rotate sen-
sor body to desired direction.
DXA.B130 DXA.B200