Cable guidance and attachment
The cable is attached to the sensing object / fume hood sash with a hook. The cable can be
damaged and/or may rip if the sensing string drags on the insertion hole or other objects.
The cable must be laid in a protected area.
The cable must be pulled straight from the sensor housing. Cable movement must be paral-
lel to sash movement; angle deflection of max. 3 degrees.
Mounting on the fume hood
Note
Do not mount the potentiometer inside the fume hood work bench.
Mount the potentiometer so that the cable travels parallel to the sash opening.
To do this, attach the sensor on the front of the fume hood. Attach the cable directly onto the
fume hood sash.
Fig. 1: DXA.B130 Mounting options.
Fig. 2: DXA.B200 Mounting options.