Data Sheet for Product

Technical Specification Sheet
Document No. 149-947
December 10, 2011
Document No. 149-947
Page 1 of 4
Fume Hood Controller
Constant Volume, 2-state (CV2)
Figure 1. Fume Hood Controller (SMT board), Enclosure and
Operator Display Panel
The 2-state Constant Volume Fume Hood Controller
is an integral part of the APOGEE® Automation
System. The controller is a proven, stand-alone
Direct Digital Control (DDC) system for laboratory
fume hoods with two discrete air flow rate set points.
The controller maintains one of two selectable and
adjustable constant volume flow rates. An Operator
Display Panel provides the fume hood user with the
operating status of the hood, alarm horn, an
emergency purge function and even optional air flow
rate. The high or low flow setpoint is selected using a
dry contact closure and/or by toggling a push-button
on the Operator Display Panel. The fume hood
controller can use either high-speed or low-speed
electronic or pneumatic actuation with either damper
or Venturi Air Valve flow control devices.
Features
Controller
Constant volume fume hood operation
High and low exhaust flow set-points
Fully integrates with the APOGEE Automation
System controllers and software
True exhaust flow measurement used to position
the flow control device
Modular components, easy to install and service
Program and calibration parameters are user
defined or modified via the Laptop Terminal
PID closed loop control for all applications
Electrically Erasable Programmable Read Only
Memory (EEPROM) memory for setpoint and
control parametersno battery needed
Supports damper and Venturi Air Valve air flow
control devices
Operator Display Panel
Continuous display of hood operating parameters
using a large alpha-numeric display
Colored hood status lights for normal (green),
marginal (yellow), and alarm (red) conditions
Purge push-button for activation of emergency
operation mode
Alarm horn for high and low face velocity indication
and emergency purge activation
Easy to install and connect to the controller via a
single cable and telephone type connectors