Data Sheet for Product

Siemens Industry, Inc.
Page 3 of 4
Agency Listings
UL 916, PAZX & CSA Certified
FCC, Class B, Subpart J
CE, C-tick
Communications
Local Area Network
(FLN trunk)
Portable Operator’s
Terminal
RS-485 4800 baud
RS-232 1200 baud
Control Performance
Speed of Response
<1 second to flow change
Airflow Measurement
Range
Accuracy*
0 2.5" wc
±3.0%
*Accuracy is shown in percent of Actual Airflow and includes differential
pressure transmitter accuracy.
Operator Display Panel
The Fume Hood Controller Operator Display Panel
(ODP) includes a custom designed package for visual
and audible indication of fume hood operating
conditions and push-buttons for emergency mode
operation, alarm silence and user defined auxiliary
functions. The panel is mounted on the fume hood in
an easy to access location and will fit over an unused
hood electrical box or over pre-drilled holes. RJ-11
type connectors provide termination to the Fume
Hood Controller and for the Portable Operator’s
Terminal. One Operator Display Panel is supported
per Fume Hood Controller.
The Operator Display Panel supports the following
functions:
Digital display of face velocity in FPM (MPS),
Green, yellow and red status lights,
Emergency purge push button,
Alarm horn with silence push button, and
Two auxiliary push buttons.
The face velocity display also indicates high and low
alarm conditions, emergency purge activation, and
diagnostic failure mode conditions when the controller
is in the minimum flow mode. Face velocity FPM
(MPS) display may be blanked as an option for
applications where the user does not desire the face
velocity reading.
Operator Display Panel
Specifications
Face Velocity Display
Range
0 fpm to 255 fpm
(0.0 MPS to 1.3 MPS)
Display Resolution 1 fpm adjustable
up to 255 fpm
Push-Buttons Switch
inputs
1 Emergency Purge
1 Horn Silence
2 Momentary Auxiliary
Alarm Horn 85 dB @ 4" (10 cm)
Dimensions 5.5" H x 3.125" W x 1.5" D
(140 mm x 80 mm x 39 mm)
Weight 8 oz. (0.2 kg)
Fume Hood Controller
Communication
Compatible with the Modular Building Controller
(MBC), Mechanical Equipment Controller (MEC) and
FLN Controller, up to 32 Fume Hood Controllers can
be connected to each one of a field panel’s three FLN
Trunks, for a total of 96 per field panel.
Operators can communicate with the Fume Hood
Controller from any field panel on the system network.
The APOGEE Automation System network does not
require additional hardware to connect controllers.
When Fume Hood Controllers are networked to an
MBC, MEC or FLN Controller, all the APOGEE
Automation System features available can utilize the
Fume Hood Controller.
Portable Operator’s Terminal
The laptop computer serving as the Portable
Operator’s Terminal can communicate with the Fume
Hood Controller. The terminal connects to the
controller via a plug-in jack on the ODP. The terminal
can be used to remotely adjust setpoints, to
troubleshoot and start up the system. The terminal
uses full English language prompting for all functions,
eliminating the need to remember coded commands.