Installation Instructions
Installation Instructions
Document No. 546-00321
Rev. 3, February, 2000
FHM Hood Evaluation Kit
Page 1 of 7
Product Description
The FHM Hood Evaluation Kit includes basic
supplies necessary to efficiently determine the most
ideal location for a sidewall adapter or sampling
tube. The purpose of these instructions is to explain
various methods used to identify an optimal location
so that the FHM may achieve optimum accuracy.
These instructions contain the basic criteria used to
determine the ideal location and concepts behind
building an averaging tube, if a fume hood requires
one. Additional materials needed are available
locally or are available for order through the Field
Purchasing Guide.
NOTE:
The Siemens Fume Hood Monitor was
designed to indicate face velocity for a
single vertical sash fume hood that is less
than 8 ft. wide. When it is used on older,
more turbulent hoods, or multi-sash fume
hoods, some special modifications may be
necessary.
NOTE:
The Fume Hood Monitor uses “through-
the-wall” technology. The flow is measured
by a single point hot-wire anemometer in
the display unit, connected by a flexible
tube through the sidewall of the hood. The
location and shape of the mobile sample
tube can be critical to achieving specified
velocity measurement accuracy. A few
inexpensive parts (included in this Kit)
allow the user to locate the ideal position
and configuration for the sample tube.
Product Numbers
546-320 FHM Hood Evaluation Kit
Kit Contents
• 3 ft. of flexible tubing
• Mobile Sample Tube
• 24 Vac transformer
Required / Optional Equipment
• Fume Hood Monitor
(546-00303A or R546-00303A)
• 1/2 inch masking tape to cover holes on the
side and end of Sample Tube
• Duct tape to secure sample tube temporarily
in location
• Ventilation Smoke Tube Kit (optional)
NOTE:
The Ventilation Smoke Tube Kit may be
ordered from the Field Purchasing Guide
(MSA 458481).
Expected Evaluation Time
5 to 30 minutes
NOTE:
Installation time is evaluated upon finding
the ideal location for the sidewall adapter.
Prerequisites
• If this is your first FHM Hood Evaluation
installation, then read these instructions
entirely before beginning the installation.
• TheFumeHood
must
be balanced before
determining the sidewall adapter location.