Basic Documentation

Table Of Contents
Terminal Equipment
Noise Problem Potential Remedy
Excessive Room Supply Air Diffuser Sound
This is usually a higher pitched whistling sound caused
by a high pressure drop across air diffusers. (Ensure the
problem is the diffuser by removing it and noting if a
substantial reduction in the sound level occurs.)
Ensure that the flexible duct at the connection to the
diffusers is in relatively good vertical alignment. The
connecting duct should be relatively straight for 1 to 2
duct diameters immediately prior to the diffuser collar.
Where multiple diffusers serve a space, ensure that
the airflow volume is equally divided among the
diffusers.
Fully open the diffuser throttling damper. Add any
necessary throttling damper(s) farther upstream,
nearer to the air terminal unit.
Replace the diffusers with larger ones or those with a
significantly lower sound rating.
Excessive Room Exhaust Air Sound
This may be due to a sound source located close to the
exhaust grille in a ceiling plenum arrangement, or to the
exhaust system itself. Exhaust system noise is usually
higher pitched sound often caused by a high pressure
drop across the air grille. (Ensure the problem is the grille
by removing it and noting if a substantial reduction in the
sound level occurs.)
When an exhaust plenum is used above the room
ceiling, determine if the sound is actually due to a
piece of equipment (such as, terminal unit) located
close to the exhaust grille. If so, relocate the exhaust
grille away from the noise source.
In ducted exhaust systems, ensure the duct
centerline is relatively straight for 1 to 2 duct
diameters immediately prior to the grille assembly
collar.
Replace the grille assembly with a larger one or
multiple grilles if the problem is due to high airflow
through the grille.
Lower the static pressure in the exhaust system to
prevent excessive pressure drops.
Seal the exhaust system to minimize any excess
airflow that is caused by leaks into the system.
Noise Transmission From Another Area
Use lined ductwork between the noisy area and the
affected areas.
Locate the duct termination point in the source room
to a location less susceptible to picking up the sound.
(Avoid locations directly above or near sound
producing equipment.)
If possible, add a lined S curve in the duct connecting
to the noisy area.
Lower the sound at the source by enclosing the
equipment within a sound absorbing enclosure.
Reduce the overall sound level in the source room by
using wall and ceiling sound absorption (acoustical)
linings.
Siemens Building Technologies, Inc. 99