Installation Instructions

Document No. 570-134
Installation Instructions
October 26, 2016
Siemens Industry, Inc. Page 3 of 7
CAUTION
DO Wiring Each DO provides a
Normally Open (NO) terminal and a
Common (C) terminal.
To reduce noise and the potential for
ground loops, both connections of a
24 Vac load must be wired directly to
the DO terminal on the controller
board.
Raccordement des sorties
numériques (DO) – chaque DO se
compose d’une borne normalement
ouverte (NO) et d’une borne
commune (C).
Afin de réduire les emissions sonores
et d’éviter de créer des boucles de
terre, les deux connexions à une
charge de 24 Vac doivent être
directement raccordées à la borne
DO sur la carte contrôleur.
8.
Plug the room temperature sensor cable into
the RTS port.
9.
Connect the power trunk. DO NOT apply
power to the controller without first consulting
the specialist.
CAUTION
It is important that the neutral that
supplies the TEC must be earth
grounded at the source of the 24 Vac
power.
Possible erratic equipment operation
or damage if neutral is not grounded.
Il est très important que le neutre qui
alimente le TEC soit mis à la terre à
la source de l’alimentation 24 Vca.
Risque de fonctionnement incohérent
de l’équipement ou de dégats si le
neutre n’est pas mis à la terre.
The installation is complete.
Smoke Control Compliance
The following instructions and information apply if
used for smoke control sequence.
1. Install Smoke Control Listed products, enclosure
and transformer. See the
Product Numbers
and
Accessories
sections for more information.
2. Input Rating:
24V 60 Hz 60 VA maximum
3. Digital Output (DO) are the only I/O authorized
for smoke control applications.
Digital Output (DO) Electrical Ratings:
5 VA per DO/ maximum 40 VA total
4. The room temperature sensor (RTS) is installed
in the same area as the TEC.
5. Connection from the TEC to the field panel is a
maximum 4000 feet, 24 AWG minimum.
6. Wiring Range:
Transformer: primary 14 AWG
24 Vac Input Power: 14 to 18 AWG
DO: AI: 18 to 20 AWG
DI: 18 AWG
LAN: 20 to 24 AWG
RST: 24 AWG
All circuits are power limited; FLN is RS-485,
RTS is RS-232. Digital Inputs (DI) are dry
contacts.
See the following documents for more
information on configuring smoke control
applications: