Application
Point Database (Slave Mode) Application 2997
48
Siemens Industry, Inc.
Application Note, App 2928
140-1302
2015-07-07
Point Database (Slave Mode) Application 2997
Point
Number
Descriptor
Factory
Default (SI
Units)
Eng Units
(SI Units)
Slope
(SI Units)
Intercept
(SI Units)
On Text
Off Text
1
CTLR ADDRESS
99
--
1
0
--
--
2
APPLICATION
2997
--
1
0
--
--
3
TEMP OFFSET
0.0 (0.0)
DEG F
(DEG C)
0.25 (0.14)
-31.75(-17.78)
--
--
{04}
ROOM TEMP
74.0
(23.44888)
DEG F
(DEG C)
0.25 (0.14)
48.0 (8.88888)
--
--
{13}
ROOM STPT
74.0
(23.44888)
DEG F
(DEG C)
0.25 (0.14)
48.0 (8.88888)
--
--
{14}
AI 4
0
PCT
0.1
0
--
--
{15}
AI 3
0
VOLTS
0.01
0
--
--
{19}
OCC BUTTON
OFF
--
--
--
ON
OFF
{21}
OCC.UNOCC
OCC
--
--
--
UNOCC
OCC
{23}
NET ALM CMD
OFF
--
--
--
ON
OFF
{24}
DI 2
OFF
--
--
--
ON
OFF
{25}
BUTTON CMD
OCC
--
--
--
UNOCC
OCC
{27}
DI 6
OFF
--
--
--
ON
OFF
{30}
AIR VOLUME 2
0 (0.0)
CFM (LPS)
4 (1.8876)
0
--
--
{35}
AIR VOLUME 1
0 (0.0)
CFM (LPS)
4 (1.8876)
0
--
--
36
FLOW COEF 1
0.73
--
0.01
0
--
--
{37}
AO1
0
VOLTS
0.01
0
--
--
{41}
DO 1
OFF
--
--
--
ON
OFF
{42}
DO 2
OFF
--
--
--
ON
OFF
{43}
DO 3
OFF
--
--
--
ON
OFF
{44}
DO 4
OFF
--
--
--
ON
OFF
{46}
DO 5
OFF
--
--
--
ON
OFF
{47}
DO 7
OFF
--
--
--
ON
OFF
{48}
DO 8
OFF
--
--
--
ON
OFF
54
FLOW COEF 2
0.73
--
0.01
0
--
--
{55}
AO2
0
VOLTS
0.01
0
--
--
{56}
AO3
0
VOLTS
0.01
0
--
--
60
DUCT AREA 2
1.0 (0.09292)
SQ. FT (SQ
M)
0.025
(0.002323)
0
--
--
{77}
DO 6
OFF
--
--
--
ON
OFF
{78}
CTL TEMP
74.0
(23.44888)
DEG F
(DEG C)
0.25 (0.14)
48.0 (8.88888)
--
--