Basic Documentation
Table Of Contents
- Introduction
- Applicable Definitions (Alphabetical Listing)
- Laboratory Safety
- Hazard Assessment
- Chemical Hygiene Plan
- Chemical Hygiene Responsibilities
- Fume Hoods
- When Required & Safe Usage
- Gloveboxes:
- Face Velocity
- Face Velocity Setback
- Size & ADA Compliance
- CAV (Constant Air Volume) Bypass
- CAV (Constant Air Volume) Conventional
- VAV (Variable Air Volume)
- VAV Diversity
- Automatic Sash Closure
- Safe Operation of Sashes
- Accessories, Services and Explosion Protection
- Ductless
- Auxiliary Air
- (Special Purpose) Perchloric Acid
- Room Air Cross Currents
- Minimum Exhaust
- Monitoring
- Selection Criteria and Performance Specifications
- Laboratory Design & Fume Hood Implementation
- Maintenance
- Periodic Testing
- Test Procedures
- Signage and Recordkeeping
- Shutdown Procedures
- Evaluating CAV (Constant Air Volume) Systems
- Evaluating VAV (Variable Air Volume) Systems
- Biological Laboratories
- Biosafety Level 1
- Biosafety Level 2
- Biosafety Level 3
- Biosafety Level 4
- Ventilation for Biosafety Level 1
- Ventilation for Biosafety Level 2
- Ventilation for Biosafety Level 3
- Ventilation for Biosafety Level 4, Cabinet Laboratory
- Ventilation for Biosafety Level 4, Suit Laboratory
- Containment Levels - Canada
- Containment Levels and Ventilation Requirements: Canada
- Biological Safety Cabinets and Classifications
- Biosafety Cabinet Applications
- Biosafety Cabinets – Installation and Safe Usage Recommendations
- Biosafety Cabinets – Certification and Safe Usage - Canada
- Biological Safety Cabinet Design, Construction and Performance Requirements
- Biosafety Cabinet Testing
- Ventilation Systems
- Local Ventilation -When Required
- Ventilation Rates for Animal Rooms
- Ventilation Rates for Animal Rooms
- Ventilation Rates for Biological Labs
- Ventilation Rates for Chemical Laboratories
- Ventilation rates for Storage areas
- Room Supply Air
- Supply Air Quality and Filtration
- Room and Duct Pressurization
- Human Occupancy, Room Temperature and Humidity
- Animal Rooms Room Temperature and Humidity
- Load Calculations
- Room Sound Level and Vibration
- Emergency Control Provisions
- Energy Conservation
- Monitoring
- Maintenance
- Periodic Inspection and Testing
- Periodic Inspection and Testing - Canada
- Test Records
- Management
- Exhaust Systems
- Configuration
- Leakage
- Components
- Manifolded Systems
- Air Velocity
- Stack Height and Discharge Location
- Operational Reliability
- Recirculated Air and Cross Contamination
- Materials and Fire Protection
- Commissioning
- Commissioning - Canada
- Referenced Publications
Laboratory Ventilation Codes and Standards
Siemens Industry, Inc. 98
Topic Requirement(s) Commentary
Ventilation
Rates for
Animal
Rooms
(Continued)
In some situations, the use of such a broad guideline might overventilate a
macroenvironment containing few animals, thereby wasting energy, or underventilate
a microenvironment containing many animals, allowing heat, moisture, and pollutants
to accumulate.
Modern heating, ventilation, and air conditioning (HVAC) systems (e.g., variable air
volume, or VAV, systems) allow ventilation rates to be set in accordance with heat
load and other variables. These systems offer considerable advantages with respect
to flexibility and energy conservation, but should always provide a minimum amount
of air exchange, as recommended for general use laboratories.
Individually ventilated cages (IVCs) and other types of specialized primary
enclosures, that either directly ventilate the enclosure using filtered room air or are
ventilated independently of the room, can effectively address animals’ ventilation
requirements without the need to increase macroenvironmental ventilation. However,
cautions mentioned above regarding high-velocity air should be considered.
Nevertheless, the macroenvironment should be ventilated sufficiently to address heat
loads, particulates, odors, and waste gases released from primary enclosures.
If ventilated primary enclosures have adequate filtration to address contamination
risks, air exhausted from the microenvironment may be returned to the room in which
animals are housed, although it is generally preferable to exhaust these systems
directly into the building’s exhaust system to reduce heat load and
macroenvironmental contamination.
Static isolation caging (without forced ventilation), such as that used in some types of
rodent housing, restricts ventilation. To compensate, it may be necessary to adjust
husbandry practices, including sanitation and cage change frequency, selection of
contact bedding, placement of cages in a secondary enclosure, animal densities in
cages, and/or decrease in macroenvironmental relative humidity to improve the
microenvironment and heat dissipation.
The use of recycled air to ventilate animal rooms may save energy but entails risks.
Because many animal pathogens can be airborne or travel on fomites (e.g., dust),
exhaust air recycled into HVAC systems that serve multiple rooms presents a risk of
cross contamination. Recycling air from nonanimal use areas (e.g., some human
occupancy areas and food, bedding, and supply storage areas) may require less
intensive filtration or conditioning and pose less risk of infection. The risks in some
situations, however, might be too great to consider recycling (e.g., in the case of
nonhuman primates and biohazard areas). The exhaust air to be recycled should be
filtered, at minimum, with 85-95% ASHRAE efficient filters to remove airborne
particles before it is recycled. Depending on the air source, composition, and
proportion of recycled air used (e.g., ammonia and other gases emitted from
excrement in recirculating air from animal rooms), consideration should also be given
to filtering volatile substances.
(Continued on Next Page)