Basic Documentation
Table Of Contents
- Introduction
- Applicable Definitions (Alphabetical Listing)
- Laboratory Safety
- Hazard Assessment
- Chemical Hygiene Plan
- Chemical Hygiene Responsibilities
- Fume Hoods
- When Required & Safe Usage
- Gloveboxes:
- Face Velocity
- Face Velocity Setback
- Size & ADA Compliance
- CAV (Constant Air Volume) Bypass
- CAV (Constant Air Volume) Conventional
- VAV (Variable Air Volume)
- VAV Diversity
- Automatic Sash Closure
- Safe Operation of Sashes
- Accessories, Services and Explosion Protection
- Ductless
- Auxiliary Air
- (Special Purpose) Perchloric Acid
- Room Air Cross Currents
- Minimum Exhaust
- Monitoring
- Selection Criteria and Performance Specifications
- Laboratory Design & Fume Hood Implementation
- Maintenance
- Periodic Testing
- Test Procedures
- Signage and Recordkeeping
- Shutdown Procedures
- Evaluating CAV (Constant Air Volume) Systems
- Evaluating VAV (Variable Air Volume) Systems
- Biological Laboratories
- Biosafety Level 1
- Biosafety Level 2
- Biosafety Level 3
- Biosafety Level 4
- Ventilation for Biosafety Level 1
- Ventilation for Biosafety Level 2
- Ventilation for Biosafety Level 3
- Ventilation for Biosafety Level 4, Cabinet Laboratory
- Ventilation for Biosafety Level 4, Suit Laboratory
- Containment Levels - Canada
- Containment Levels and Ventilation Requirements: Canada
- Biological Safety Cabinets and Classifications
- Biosafety Cabinet Applications
- Biosafety Cabinets – Installation and Safe Usage Recommendations
- Biosafety Cabinets – Certification and Safe Usage - Canada
- Biological Safety Cabinet Design, Construction and Performance Requirements
- Biosafety Cabinet Testing
- Ventilation Systems
- Local Ventilation -When Required
- Ventilation Rates for Animal Rooms
- Ventilation Rates for Animal Rooms
- Ventilation Rates for Biological Labs
- Ventilation Rates for Chemical Laboratories
- Ventilation rates for Storage areas
- Room Supply Air
- Supply Air Quality and Filtration
- Room and Duct Pressurization
- Human Occupancy, Room Temperature and Humidity
- Animal Rooms Room Temperature and Humidity
- Load Calculations
- Room Sound Level and Vibration
- Emergency Control Provisions
- Energy Conservation
- Monitoring
- Maintenance
- Periodic Inspection and Testing
- Periodic Inspection and Testing - Canada
- Test Records
- Management
- Exhaust Systems
- Configuration
- Leakage
- Components
- Manifolded Systems
- Air Velocity
- Stack Height and Discharge Location
- Operational Reliability
- Recirculated Air and Cross Contamination
- Materials and Fire Protection
- Commissioning
- Commissioning - Canada
- Referenced Publications
Laboratory Ventilation Codes and Standards
Siemens Industry, Inc. 118
Topic Requirement(s) Commentary
Energy
Conservation
(Continued)
ASHRAE, 2011 Handbook - HVAC Applications, Laboratories, Pg. 16.18 – 16.19
ENERGY
Efforts to reduce energy use must not compromise standards established by safety
officers.
Energy reduction systems must maintain required environmental conditions during
both occupied and unoccupied modes.
Energy can be used more efficiently in laboratories by reducing exhaust air
requirements. One way to achieve this is to use variable volume control of exhaust air
through the fume hoods to reduce exhaust airflow when the fume hood sash is not fully
open. Any airflow control must be integrated with the laboratory control system,
described in the section on Control, and must not jeopardize the safety and function of
the laboratory.
Setback controls that reduce ventilation rates when the laboratory is unoccupied can
also reduce energy consumption. Timing devices, sensors, manual override, or a
combination of these can be used to set back the controls at night. If this strategy is a
possibility, the safety and function of the laboratory must be considered, and
appropriate safety officers should be consulted.
Fume hood selection also impacts exhaust airflow requirements and energy
consumption. Modern fume hood designs use several techniques to reduce airflow
requirements, including reduced face opening sashes and specifically designed
components that allow operation with reduced inflow velocities.
Energy can often be recovered economically from the exhaust airstream in laboratory
buildings with large quantities of exhaust air. Many energy recovery systems are
available, including rotary air to-air energy exchangers or heat wheels, coil energy
recovery loops(runaround cycle), twin tower enthalpy recovery loops, heat pipe heat
exchangers, fixed-plate heat exchangers, thermo siphon heat exchangers, and direct
evaporative cooling. Some of these technologies can be combined with indirect
evaporative cooling for further energy recovery.
Concerns about the use of energy recovery devices in laboratory HVAC systems
include (1) the potential for cross-contamination of chemical and biological materials
from exhaust air to the intake airstream, and (2) the potential for corrosion and fouling
of devices located in the exhaust airstream. NFPA Standard 45 specifically prohibits
the use of latent heat recovery devices in fume hood exhaust systems.
Energy recovery is also possible for hydronic systems associated with HVAC. Rejected
heat from centrifugal chillers can be used to produce low-temperature reheat water.
Potential also exists in plumbing systems, where waste heat from washing operations
can be recovered to heat makeup water.
Energy recovery systems for laboratory
applications require considerable more
careful examination than such systems for
non-laboratory applications mainly due to the
potential for cross-contamination and
corrosion.