Basic Documentation
Table Of Contents
- Introduction
- Applicable Definitions (Alphabetical Listing)
- Laboratory Safety
- Hazard Assessment
- Chemical Hygiene Plan
- Chemical Hygiene Responsibilities
- Fume Hoods
- When Required & Safe Usage
- Gloveboxes:
- Face Velocity
- Face Velocity Setback
- Size & ADA Compliance
- CAV (Constant Air Volume) Bypass
- CAV (Constant Air Volume) Conventional
- VAV (Variable Air Volume)
- VAV Diversity
- Automatic Sash Closure
- Safe Operation of Sashes
- Accessories, Services and Explosion Protection
- Ductless
- Auxiliary Air
- (Special Purpose) Perchloric Acid
- Room Air Cross Currents
- Minimum Exhaust
- Monitoring
- Selection Criteria and Performance Specifications
- Laboratory Design & Fume Hood Implementation
- Maintenance
- Periodic Testing
- Test Procedures
- Signage and Recordkeeping
- Shutdown Procedures
- Evaluating CAV (Constant Air Volume) Systems
- Evaluating VAV (Variable Air Volume) Systems
- Biological Laboratories
- Biosafety Level 1
- Biosafety Level 2
- Biosafety Level 3
- Biosafety Level 4
- Ventilation for Biosafety Level 1
- Ventilation for Biosafety Level 2
- Ventilation for Biosafety Level 3
- Ventilation for Biosafety Level 4, Cabinet Laboratory
- Ventilation for Biosafety Level 4, Suit Laboratory
- Containment Levels - Canada
- Containment Levels and Ventilation Requirements: Canada
- Biological Safety Cabinets and Classifications
- Biosafety Cabinet Applications
- Biosafety Cabinets – Installation and Safe Usage Recommendations
- Biosafety Cabinets – Certification and Safe Usage - Canada
- Biological Safety Cabinet Design, Construction and Performance Requirements
- Biosafety Cabinet Testing
- Ventilation Systems
- Local Ventilation -When Required
- Ventilation Rates for Animal Rooms
- Ventilation Rates for Animal Rooms
- Ventilation Rates for Biological Labs
- Ventilation Rates for Chemical Laboratories
- Ventilation rates for Storage areas
- Room Supply Air
- Supply Air Quality and Filtration
- Room and Duct Pressurization
- Human Occupancy, Room Temperature and Humidity
- Animal Rooms Room Temperature and Humidity
- Load Calculations
- Room Sound Level and Vibration
- Emergency Control Provisions
- Energy Conservation
- Monitoring
- Maintenance
- Periodic Inspection and Testing
- Periodic Inspection and Testing - Canada
- Test Records
- Management
- Exhaust Systems
- Configuration
- Leakage
- Components
- Manifolded Systems
- Air Velocity
- Stack Height and Discharge Location
- Operational Reliability
- Recirculated Air and Cross Contamination
- Materials and Fire Protection
- Commissioning
- Commissioning - Canada
- Referenced Publications
Ventilation Systems
Siemens Industry, Inc. 125
Topic Requirement(s) Commentary
Periodic
Inspection
and Testing
- Canada
(Continued)
• Containment Level 4 Additional Room Integrity Testing:
Integrity of containment to be tested by pressure decay testing. Acceptance criteria:
two consecutive tests with a minimum of 250 Pa (1 in. w.g.) loss of pressure from
an initial 500 Pa (2 in. w.g.) over a 20 minute period.
This test is not a mandatory requirement for recertification if no modification or
changes have been made that will affect the integrity of the laboratory, and if a
visual inspection of the containment barrier membrane indicates that the integrity
has not been compromised; if the perimeter integrity is suspect upon visual
inspection, the requirement for repeating the pressure decay test should be
determined in consultation with the laboratory supervisor, Biological Safety
Officer/Institutional Biosafety Committee.
5.2.2 Room Pressure Decay Testing
The basic procedure for room pressure decay testing under negative pressure is as
follows:
• Isolate the area by closing and securing all doors, valves and bubble tight dampers
at the containment barrier (avoid temporary sealing measures in doors, windows
and services that would cover permanent seals and not permit their testing for
leakage); plug all pressure sensor lines, e.g., magnehelic gauges.
• Install a calibrated inclined manometer across the containment barrier such that it
is not affected by air distribution. Manometer to have minimum accuracy of 10 Pa
(0.05 in. w.g.) and capable of reading pressure up to 750 Pa (3 in. w.g.).
• Install a ball valve in the piping between the vacuum pump/fan and the room to
allow the room to be sealed once the test pressure has been attained.
• Connect a vacuum source to the room and create a 500 Pa (2 in. w.g.) negative
pressure differential; allow room to stabilize and close the valve between the
vacuum pump/fan and the room to seal room at 500 Pa (2 in. w.g.).
• Dynamically trend pressure loss starting at 500 Pa (2 in. w.g.) negative pressure
differential; record the differential pressure at 1 minute intervals for 20 minutes.
• If repeat test is required, allow 20 minute wait period.
• Disconnect the vacuum pump/fan and open the ball valve slowly to allow room
pressure to return to normal condition.
• If leak rate exceeds the acceptance value:
• pressurize the room to a pressure adequate to locate leaks;
(Continued on Next Page)