Basic Documentation
Table Of Contents
- Introduction
- Applicable Definitions (Alphabetical Listing)
- Laboratory Safety
- Hazard Assessment
- Chemical Hygiene Plan
- Chemical Hygiene Responsibilities
- Fume Hoods
- When Required & Safe Usage
- Gloveboxes:
- Face Velocity
- Face Velocity Setback
- Size & ADA Compliance
- CAV (Constant Air Volume) Bypass
- CAV (Constant Air Volume) Conventional
- VAV (Variable Air Volume)
- VAV Diversity
- Automatic Sash Closure
- Safe Operation of Sashes
- Accessories, Services and Explosion Protection
- Ductless
- Auxiliary Air
- (Special Purpose) Perchloric Acid
- Room Air Cross Currents
- Minimum Exhaust
- Monitoring
- Selection Criteria and Performance Specifications
- Laboratory Design & Fume Hood Implementation
- Maintenance
- Periodic Testing
- Test Procedures
- Signage and Recordkeeping
- Shutdown Procedures
- Evaluating CAV (Constant Air Volume) Systems
- Evaluating VAV (Variable Air Volume) Systems
- Biological Laboratories
- Biosafety Level 1
- Biosafety Level 2
- Biosafety Level 3
- Biosafety Level 4
- Ventilation for Biosafety Level 1
- Ventilation for Biosafety Level 2
- Ventilation for Biosafety Level 3
- Ventilation for Biosafety Level 4, Cabinet Laboratory
- Ventilation for Biosafety Level 4, Suit Laboratory
- Containment Levels - Canada
- Containment Levels and Ventilation Requirements: Canada
- Biological Safety Cabinets and Classifications
- Biosafety Cabinet Applications
- Biosafety Cabinets – Installation and Safe Usage Recommendations
- Biosafety Cabinets – Certification and Safe Usage - Canada
- Biological Safety Cabinet Design, Construction and Performance Requirements
- Biosafety Cabinet Testing
- Ventilation Systems
- Local Ventilation -When Required
- Ventilation Rates for Animal Rooms
- Ventilation Rates for Animal Rooms
- Ventilation Rates for Biological Labs
- Ventilation Rates for Chemical Laboratories
- Ventilation rates for Storage areas
- Room Supply Air
- Supply Air Quality and Filtration
- Room and Duct Pressurization
- Human Occupancy, Room Temperature and Humidity
- Animal Rooms Room Temperature and Humidity
- Load Calculations
- Room Sound Level and Vibration
- Emergency Control Provisions
- Energy Conservation
- Monitoring
- Maintenance
- Periodic Inspection and Testing
- Periodic Inspection and Testing - Canada
- Test Records
- Management
- Exhaust Systems
- Configuration
- Leakage
- Components
- Manifolded Systems
- Air Velocity
- Stack Height and Discharge Location
- Operational Reliability
- Recirculated Air and Cross Contamination
- Materials and Fire Protection
- Commissioning
- Commissioning - Canada
- Referenced Publications
Ventilation Systems
Siemens Industry, Inc. 129
Topic Requirement(s) Commentary
Periodic
Inspection
and Testing -
Canada
(Continued)
9. Supply and exhaust air ductwork between containment perimeter and HEPA filter
or bubble tight backdraft damper to be tested in situ by pressure decay method in
accordance with ASME N510(2). Acceptance criteria: rate of air leakage not to
exceed 0.1% duct vol/min at 1000 Pa (4 in. w.g.) minimum test pressure.
10. Pressurization relationships across adjacent areas to be verified (that is, clean
change to dirty change, dirty change to laboratory). Acceptance criteria: inward
directional airflow (under normal operations) to be visually demonstrated (e.g., by
holding a smoke pencil at each door leading to adjacent areas).
11. Control systems to be tested for fail-safe operation by failure of system
components, (that is, exhaust fan failure, supply fan failure, power failure [where
possible], Class II B2 BSC exhaust failure). This is to include audible/visual alarm
testing. Acceptance criteria: inward directional airflow. The sustained reversal of
airflow across containment barrier is to be prevented. This test is not a mandatory
requirement for recertification if no control system hardware or logic changes or
upgrades have been done; if modifications have been performed, or if frequent
control system problems or failures have been encountered, then the requirement
for retesting should be determined in consultation with the Biological Safety
Officer/ Institutional Biosafety Committee. Note, this may necessitate the need for
decontamination. While not required annually, control systems should be retested
periodically. Consult Manufacturer's specifications.
12. Supply and exhaust air ductwork between containment perimeter and HEPA filter
or bubble tight backdraft damper to be tested in situ by pressure decay method in
accordance with ASME N510(2). Acceptance criteria: rate of air leakage not to
exceed 0.1% duct vol/min at 1000 Pa (4 in. w.g.) minimum test pressure.
13. Pressurization relationships across adjacent areas to be verified (that is, clean
change to dirty change, dirty change to laboratory). Acceptance criteria: inward
directional airflow (under normal operations) to be visually demonstrated (e.g., by
holding a smoke pencil at each door leading to adjacent areas).
14. Control systems to be tested for fail-safe operation by failure of system
components, (that is, exhaust fan failure, supply fan failure, power failure [where
possible], Class II B2 BSC exhaust failure). This is to include audible/visual alarm
testing. Acceptance criteria: inward directional airflow. The sustained reversal of
airflow across containment barrier is to be prevented. This test is not a mandatory
requirement for recertification if no control system hardware or logic changes or
upgrades have been done; if modifications have been performed, or if frequent
control system problems or failures have been encountered, then the requirement
for retesting should be determined in consultation with the Biological Safety
Officer/ Institutional Biosafety Committee. Note, this may necessitate the need for
decontamination. While not required annually, control systems should be retested
periodically. Consult Manufacturer's specifications.
Footnotes for Containment Level 4 (CL4) Testing Requirements are listed on the
following page.