Basic Documentation
Table Of Contents
- Introduction
- Applicable Definitions (Alphabetical Listing)
- Laboratory Safety
- Hazard Assessment
- Chemical Hygiene Plan
- Chemical Hygiene Responsibilities
- Fume Hoods
- When Required & Safe Usage
- Gloveboxes:
- Face Velocity
- Face Velocity Setback
- Size & ADA Compliance
- CAV (Constant Air Volume) Bypass
- CAV (Constant Air Volume) Conventional
- VAV (Variable Air Volume)
- VAV Diversity
- Automatic Sash Closure
- Safe Operation of Sashes
- Accessories, Services and Explosion Protection
- Ductless
- Auxiliary Air
- (Special Purpose) Perchloric Acid
- Room Air Cross Currents
- Minimum Exhaust
- Monitoring
- Selection Criteria and Performance Specifications
- Laboratory Design & Fume Hood Implementation
- Maintenance
- Periodic Testing
- Test Procedures
- Signage and Recordkeeping
- Shutdown Procedures
- Evaluating CAV (Constant Air Volume) Systems
- Evaluating VAV (Variable Air Volume) Systems
- Biological Laboratories
- Biosafety Level 1
- Biosafety Level 2
- Biosafety Level 3
- Biosafety Level 4
- Ventilation for Biosafety Level 1
- Ventilation for Biosafety Level 2
- Ventilation for Biosafety Level 3
- Ventilation for Biosafety Level 4, Cabinet Laboratory
- Ventilation for Biosafety Level 4, Suit Laboratory
- Containment Levels - Canada
- Containment Levels and Ventilation Requirements: Canada
- Biological Safety Cabinets and Classifications
- Biosafety Cabinet Applications
- Biosafety Cabinets – Installation and Safe Usage Recommendations
- Biosafety Cabinets – Certification and Safe Usage - Canada
- Biological Safety Cabinet Design, Construction and Performance Requirements
- Biosafety Cabinet Testing
- Ventilation Systems
- Local Ventilation -When Required
- Ventilation Rates for Animal Rooms
- Ventilation Rates for Animal Rooms
- Ventilation Rates for Biological Labs
- Ventilation Rates for Chemical Laboratories
- Ventilation rates for Storage areas
- Room Supply Air
- Supply Air Quality and Filtration
- Room and Duct Pressurization
- Human Occupancy, Room Temperature and Humidity
- Animal Rooms Room Temperature and Humidity
- Load Calculations
- Room Sound Level and Vibration
- Emergency Control Provisions
- Energy Conservation
- Monitoring
- Maintenance
- Periodic Inspection and Testing
- Periodic Inspection and Testing - Canada
- Test Records
- Management
- Exhaust Systems
- Configuration
- Leakage
- Components
- Manifolded Systems
- Air Velocity
- Stack Height and Discharge Location
- Operational Reliability
- Recirculated Air and Cross Contamination
- Materials and Fire Protection
- Commissioning
- Commissioning - Canada
- Referenced Publications
Laboratory Ventilation Codes and Standards
Siemens Industry, Inc. 146
Topic Requirement(s) Commentary
Recirculated
Air and Cross
Contamination
(Continued)
Institute of Laboratory Animal Research, Commission on Life Sciences,
National Research Council, Guide for the Care and Use of Laboratory Animals,
Eight Edition, 2011:
Page 46: The use of recycled air to ventilate animal rooms saves considerable
amounts of energy but might entail some risk. Many animal pathogens can be
airborne or travel on fomites, such as dust, so exhaust air to be recycled into
heating, ventilation, and air-conditioning systems that serve multiple rooms presents
a risk of cross contamination. The exhaust air to be recycled should be HEPA
filtered (high-efficiency particulate air-filtered) to remove airborne particles before it
is recycled; the extent and efficiency of filtration should be proportional to the
estimated risk.
Air that does not originate from animal use areas but has been used to ventilate
other spaces (e.g., some human-occupancy areas and food, bedding, and supply
storage areas) may be recycled for animal space ventilation and might require less-
intensive filtration or conditioning than air recycled from animal use space.
Toxic or odor-causing gases, such as ammonia, can be kept within acceptable limits
if they are removed by the ventilation system and replaced with air that contains
either a lower concentration or none of these gases. Treatment of recycled air for
these substances by chemical absorption or scrubbing might be effective; however,
the use of nonrecycled air is preferred for ventilation of animal use and holding
areas. The use of HEPA filtered recycled air without gaseous filtration (such as with
activated-charcoal filters) can be used but only that:
• Room air is mixed with at least 50% fresh air (that is, the supply air does not
exceed 50% recycled air).
• Recycled air is returned only to the room or area from which it was generated,
except if it comes from other than animal housing areas.
• Recycled air is appropriately conditioned and mixed with sufficient fresh air to
address the thermal and humidity requirements of animals in that space.
See applicable commentary on the previous
page.