Basic Documentation
Table Of Contents
- Introduction
- Applicable Definitions (Alphabetical Listing)
- Laboratory Safety
- Hazard Assessment
- Chemical Hygiene Plan
- Chemical Hygiene Responsibilities
- Fume Hoods
- When Required & Safe Usage
- Gloveboxes:
- Face Velocity
- Face Velocity Setback
- Size & ADA Compliance
- CAV (Constant Air Volume) Bypass
- CAV (Constant Air Volume) Conventional
- VAV (Variable Air Volume)
- VAV Diversity
- Automatic Sash Closure
- Safe Operation of Sashes
- Accessories, Services and Explosion Protection
- Ductless
- Auxiliary Air
- (Special Purpose) Perchloric Acid
- Room Air Cross Currents
- Minimum Exhaust
- Monitoring
- Selection Criteria and Performance Specifications
- Laboratory Design & Fume Hood Implementation
- Maintenance
- Periodic Testing
- Test Procedures
- Signage and Recordkeeping
- Shutdown Procedures
- Evaluating CAV (Constant Air Volume) Systems
- Evaluating VAV (Variable Air Volume) Systems
- Biological Laboratories
- Biosafety Level 1
- Biosafety Level 2
- Biosafety Level 3
- Biosafety Level 4
- Ventilation for Biosafety Level 1
- Ventilation for Biosafety Level 2
- Ventilation for Biosafety Level 3
- Ventilation for Biosafety Level 4, Cabinet Laboratory
- Ventilation for Biosafety Level 4, Suit Laboratory
- Containment Levels - Canada
- Containment Levels and Ventilation Requirements: Canada
- Biological Safety Cabinets and Classifications
- Biosafety Cabinet Applications
- Biosafety Cabinets – Installation and Safe Usage Recommendations
- Biosafety Cabinets – Certification and Safe Usage - Canada
- Biological Safety Cabinet Design, Construction and Performance Requirements
- Biosafety Cabinet Testing
- Ventilation Systems
- Local Ventilation -When Required
- Ventilation Rates for Animal Rooms
- Ventilation Rates for Animal Rooms
- Ventilation Rates for Biological Labs
- Ventilation Rates for Chemical Laboratories
- Ventilation rates for Storage areas
- Room Supply Air
- Supply Air Quality and Filtration
- Room and Duct Pressurization
- Human Occupancy, Room Temperature and Humidity
- Animal Rooms Room Temperature and Humidity
- Load Calculations
- Room Sound Level and Vibration
- Emergency Control Provisions
- Energy Conservation
- Monitoring
- Maintenance
- Periodic Inspection and Testing
- Periodic Inspection and Testing - Canada
- Test Records
- Management
- Exhaust Systems
- Configuration
- Leakage
- Components
- Manifolded Systems
- Air Velocity
- Stack Height and Discharge Location
- Operational Reliability
- Recirculated Air and Cross Contamination
- Materials and Fire Protection
- Commissioning
- Commissioning - Canada
- Referenced Publications
Laboratory Ventilation Codes and Standards
Siemens Industry, Inc. 30
Topic Requirement(s) Commentary
Accessories,
Services and
Explosion
Protection
National Fire Protection Association, Standard NFPA 45, 2011
8.2.3 Chemical fume hoods shall not be relied upon to provide explosion (blast)
protection unless specifically designed to do so.
A.8.2.3 Hoods having explosionproof electrical devices are sometimes referred to as
explosionproof hoods. This term does not imply that they will contain an explosion,
only that the electrical equipment will not provide a source of ignition.
American National Standard for Laboratory Ventilation, ANSI/AIHA Z9.5-2003
1.1 This standard does not apply to the following types of laboratories or hoods
except as it may relate to general laboratory ventilation:
• Explosives laboratories;
• Radioisotope laboratories;
• Laminar flow hoods (e.g., a clean bench for product protection, not employee
protection);
• Biological safety cabinets.
Scientific Equipment & Furniture Association
SEFA 1–2006 Recommended Practices for Laboratory Fume Hoods
4.1.9 Many hood manufacturers can equip hoods with a variety of amenities or
services. The more popular services include electrical outlets, sinks, fixtures and
plumbing for gas vacuum, and air. For increased safety, controls for these services
should always be accessible from outside the hood opening.
Service Fixtures All service fixtures shall be installed so that service supply lines
can be connected or disconnected, either by design of the piping assembly or
through an access panel in the hood interior or exterior. All service valves shall be
accessible for maintenance. All service fixture controls (e.g., gas, air, water, vacuum)
should be external to the hood interior, clearly identified and within easy reach. All
internal corrosion fixture outlets shall be corrosion resistant to the application.
Electrical Receptacles All electrical receptacles should be readily accessible.
Provision shall be made so that all electrical wiring will be isolated and physically
separated from vapors handled within the hood interior after the fume hood is
installed. The receptacle shall be installed with the ground outlet above the power
slots.
Although a conventional laboratory fume hood
with a closed sash may provide protection
from an active chemical reaction or even a
‘small’ detonation, they are not typically
designed to provide explosion protection and
should not be used in applications where an
explosion hazard exists.
In order to not have a source of ignition
present at the fume hood, all of the hood’s
internal and external electrical fixtures (lights,
switches, outlets, etc.) have to be explosion-
proof and any equipment placed within the
fume hood interior (heaters, analyzers,
stirrers, etc.) must also be explosion-proof.