Basic Documentation
Table Of Contents
- Introduction
- Applicable Definitions (Alphabetical Listing)
- Laboratory Safety
- Hazard Assessment
- Chemical Hygiene Plan
- Chemical Hygiene Responsibilities
- Fume Hoods
- When Required & Safe Usage
- Gloveboxes:
- Face Velocity
- Face Velocity Setback
- Size & ADA Compliance
- CAV (Constant Air Volume) Bypass
- CAV (Constant Air Volume) Conventional
- VAV (Variable Air Volume)
- VAV Diversity
- Automatic Sash Closure
- Safe Operation of Sashes
- Accessories, Services and Explosion Protection
- Ductless
- Auxiliary Air
- (Special Purpose) Perchloric Acid
- Room Air Cross Currents
- Minimum Exhaust
- Monitoring
- Selection Criteria and Performance Specifications
- Laboratory Design & Fume Hood Implementation
- Maintenance
- Periodic Testing
- Test Procedures
- Signage and Recordkeeping
- Shutdown Procedures
- Evaluating CAV (Constant Air Volume) Systems
- Evaluating VAV (Variable Air Volume) Systems
- Biological Laboratories
- Biosafety Level 1
- Biosafety Level 2
- Biosafety Level 3
- Biosafety Level 4
- Ventilation for Biosafety Level 1
- Ventilation for Biosafety Level 2
- Ventilation for Biosafety Level 3
- Ventilation for Biosafety Level 4, Cabinet Laboratory
- Ventilation for Biosafety Level 4, Suit Laboratory
- Containment Levels - Canada
- Containment Levels and Ventilation Requirements: Canada
- Biological Safety Cabinets and Classifications
- Biosafety Cabinet Applications
- Biosafety Cabinets – Installation and Safe Usage Recommendations
- Biosafety Cabinets – Certification and Safe Usage - Canada
- Biological Safety Cabinet Design, Construction and Performance Requirements
- Biosafety Cabinet Testing
- Ventilation Systems
- Local Ventilation -When Required
- Ventilation Rates for Animal Rooms
- Ventilation Rates for Animal Rooms
- Ventilation Rates for Biological Labs
- Ventilation Rates for Chemical Laboratories
- Ventilation rates for Storage areas
- Room Supply Air
- Supply Air Quality and Filtration
- Room and Duct Pressurization
- Human Occupancy, Room Temperature and Humidity
- Animal Rooms Room Temperature and Humidity
- Load Calculations
- Room Sound Level and Vibration
- Emergency Control Provisions
- Energy Conservation
- Monitoring
- Maintenance
- Periodic Inspection and Testing
- Periodic Inspection and Testing - Canada
- Test Records
- Management
- Exhaust Systems
- Configuration
- Leakage
- Components
- Manifolded Systems
- Air Velocity
- Stack Height and Discharge Location
- Operational Reliability
- Recirculated Air and Cross Contamination
- Materials and Fire Protection
- Commissioning
- Commissioning - Canada
- Referenced Publications
Fume Hoods
Siemens Industry, Inc. 37
Topic Requirement(s) Commentary
Room Air
Cross Currents
U.S. OSHA, 29 CFR, Part 1910, Occupational Safety and Health Standards,
Subpart Z, Toxic and Hazardous Substances,1910.1450,C4(g):
General air flow should not be turbulent and should be relatively uniform throughout
the laboratory, with no high velocity or static areas; airflow into and within the hood
should not be excessively turbulent.
National Fire Protection Association, Standard NFPA 45, 2011
8.8.6 For auxiliary air fume hoods, auxiliary air shall be introduced exterior to the
hood face in such a manner that the airflow does not compromise the protection
provided by the hood and so that an imbalance of auxiliary air to exhaust air will not
pressurize the hood interior.
8.9.1 Chemical fume hoods shall be located in areas of minimum air turbulence.
A.8.9.1 A person walking past the hood can create sufficient turbulence to disrupt a
face velocity of 0.5 m/sec (100 ft/min). In addition, open windows or air
impingement from an air diffuser can completely negate or dramatically reduce the
face velocity and can also affect negative differential air pressure.
American National Standard for Laboratory Ventilation ANSI/AIHA Z9.5-2003
5.2.2 Supply air distribution shall be designed to keep air jet velocities less than
half, preferably less than one-third of the capture velocity or the face velocity of the
laboratory chemical hoods at their face opening.
For most laboratory chemical hoods, this requirement will mean 50 fpm (0.25 m/s)
or less terminal throw velocity at 6 ft. (1.8 m) above the floor.
6.3.5 Excessive cross draft velocities (>50% of the average face velocity) have
been demonstrated to significantly affect hood containment and should be identified
and alleviated. Ideally, cross draft velocities should be less than 30%.
Scientific Equipment & Furniture Association
SEFA 1–2006 Recommended Practices for Laboratory Fume Hoods
5.1 Location in Laboratory
Laboratory fume hoods should be so located within the laboratory to avoid
crosscurrents at the fume hood face due to heating, cooling, or ventilating inlets.
5.2 Safety Considerations
Laboratory fume hoods should be located away from high traffic lanes within the
laboratory because personnel walking past the sash opening may disrupt the flow
of air into the unit and cause turbulence, drawing hazardous fumes into the
laboratory.
(Continued on Next Page)
Virtually all standards point out that room air
currents at a fume hood’s open face area
(that is, cross drafts) can adversely affect
fume hood containment when the air currents
are above specific levels.
Excessive cross drafts typically result from:
• Improper room supply air diffusers
(conventional high velocity, mixing
diffusers rather than the perforated type).
• Having too few supply air diffusers
resulting in high supply air velocity from
each unit.
• Improper diffuser location (such as
directly above the fume hoods or on
room side walls).
• Room occupants using portable cooling
fans or having operable windows in the
open position.
• Too rapid movement of persons working
at or passing by fume hoods. Also,
having room doors open.
Both NFPA 45 and ANSI/Z9.5 recommend
that cross draft velocities should (ideally) not
exceed 30% of the average face velocity. For
a nominal 100 FPM face velocity the cross
drafts should therefore not exceed 30 FPM.
This is slightly less than 3 miles per hour
which is a person’s nominal walking speed.
For low velocity hoods, the allowable cross
draft is even lower.
Better fume hood containment can be
attained with good room air distribution than
with higher face velocities and poor air
distribution (higher cross current velocities).