Basic Documentation
Table Of Contents
- Introduction
- Applicable Definitions (Alphabetical Listing)
- Laboratory Safety
- Hazard Assessment
- Chemical Hygiene Plan
- Chemical Hygiene Responsibilities
- Fume Hoods
- When Required & Safe Usage
- Gloveboxes:
- Face Velocity
- Face Velocity Setback
- Size & ADA Compliance
- CAV (Constant Air Volume) Bypass
- CAV (Constant Air Volume) Conventional
- VAV (Variable Air Volume)
- VAV Diversity
- Automatic Sash Closure
- Safe Operation of Sashes
- Accessories, Services and Explosion Protection
- Ductless
- Auxiliary Air
- (Special Purpose) Perchloric Acid
- Room Air Cross Currents
- Minimum Exhaust
- Monitoring
- Selection Criteria and Performance Specifications
- Laboratory Design & Fume Hood Implementation
- Maintenance
- Periodic Testing
- Test Procedures
- Signage and Recordkeeping
- Shutdown Procedures
- Evaluating CAV (Constant Air Volume) Systems
- Evaluating VAV (Variable Air Volume) Systems
- Biological Laboratories
- Biosafety Level 1
- Biosafety Level 2
- Biosafety Level 3
- Biosafety Level 4
- Ventilation for Biosafety Level 1
- Ventilation for Biosafety Level 2
- Ventilation for Biosafety Level 3
- Ventilation for Biosafety Level 4, Cabinet Laboratory
- Ventilation for Biosafety Level 4, Suit Laboratory
- Containment Levels - Canada
- Containment Levels and Ventilation Requirements: Canada
- Biological Safety Cabinets and Classifications
- Biosafety Cabinet Applications
- Biosafety Cabinets – Installation and Safe Usage Recommendations
- Biosafety Cabinets – Certification and Safe Usage - Canada
- Biological Safety Cabinet Design, Construction and Performance Requirements
- Biosafety Cabinet Testing
- Ventilation Systems
- Local Ventilation -When Required
- Ventilation Rates for Animal Rooms
- Ventilation Rates for Animal Rooms
- Ventilation Rates for Biological Labs
- Ventilation Rates for Chemical Laboratories
- Ventilation rates for Storage areas
- Room Supply Air
- Supply Air Quality and Filtration
- Room and Duct Pressurization
- Human Occupancy, Room Temperature and Humidity
- Animal Rooms Room Temperature and Humidity
- Load Calculations
- Room Sound Level and Vibration
- Emergency Control Provisions
- Energy Conservation
- Monitoring
- Maintenance
- Periodic Inspection and Testing
- Periodic Inspection and Testing - Canada
- Test Records
- Management
- Exhaust Systems
- Configuration
- Leakage
- Components
- Manifolded Systems
- Air Velocity
- Stack Height and Discharge Location
- Operational Reliability
- Recirculated Air and Cross Contamination
- Materials and Fire Protection
- Commissioning
- Commissioning - Canada
- Referenced Publications
Fume Hoods
Siemens Industry, Inc. 39
Topic Requirement(s) Commentary
Minimum
Exhaust
National Fire Protection Association, Standard NFPA 45, 2011
A-8.4.7 In addition to maintaining proper fume hood face velocity, fume hoods that
reduce the exhaust In addition to maintaining proper fume hood face velocity, fume
hoods that reduce the exhaust volume as the sash opening is reduced should
maintain a minimum exhaust volume to ensure that contaminants are diluted and
exhausted from a hood. The chemical fume hood exhaust airflow should not be
reduced to less than the flow rate recommended in ANSI/AIHA Z9.5, Laboratory
Ventilation.
American National Standard for Laboratory Ventilation ANSI/AIHA Z9.5-2003
3.3.1 The mechanism that controls the exhaust fan speed or damper position to
regulate the hood exhaust volume shall be designed to ensure a minimum exhaust
volume in constant volume systems equal to the larger of 50 cfm/ft of hood width, or
25 cfm/ft
2
of hood work surface area, except where a written hazard characterization
indicates otherwise, or if the hood is not in use.
The NFPA 45 stated minimum exhaust of 25
cfm per square foot of internal hood work
surface typically equates to 20% to 25% of
the required exhaust rate for a fully open sash
and 100 fpm face velocity. Frequently this
limits the “turndown” on a VAV hood to about
5:1.
An example of where a written hazard
classification would indicate that a minimum
exhaust is not required could be where the
fume hood is used only for odor control and
where hazardous fumes are never present.
Note that in ANSIAIHA Z9.5-2003, there is a
likely typo in that the term “constant volume
systems” should probably be “variable air
volume” since VAV fume hoods and not CAV
fume hoods have a mechanism to regulate
the exhaust.