Basic Documentation

Table Of Contents
Laboratory Ventilation Codes and Standards
Siemens Industry, Inc. 40
Topic Requirement(s) Commentary
Fire
Protection/
Emergency
Control
Provisions
National Fire Protection Association, Standard NFPA 45, 2011
8.10.1 Automatic fire protection systems shall not be required in chemical fume hoods
or exhaust systems except in the following cases:
(1) Existing hoods having interiors with a flame spread index greater than 25 in which
flammable liquids are handled.
(2) If a hazard assessment shows that an automatic extinguishing system is required
for the chemical fume hood, then the applicable automatic fire suppression system
standard shall be followed.
8.10.2 Automatic fire protection systems, where provided, shall comply with the
following standards, as applicable:
(1) NFPA 11, Standard for Low, Medium, and High-Expansion Foam
(2) NFPA 12, Standard for Carbon Dioxide Extinguishing Systems
(3) NFPA 12A, Standard for Halon 1301 Fire Extinguishing Systems
(4) NFPA 13, Standard for the installation of Sprinkler Systems
(5) NFPA 15, Standard for Water Spray Fixed Systems for Fire Protection
(6) NFPA 17, Standard for Dry Chemical Extinguishing Systems
(7) NFPA 17A, Standard for Wet Chemical Extinguishing Systems
(8) NFPA 69, Standard on Explosion Prevention Systems
(9) NFPA 750, Standard on Water Mist Fire Protection Systems
(10) NFPA 2001, Standard on Clean Agent Fire Extinguishing Systems
8.10.3.1 Automatic fire dampers shall not be used in chemical fume hood exhaust
systems.
8.10.4 Fire detection and alarm systems shall not be interlocked to automatically shut
down chemical fume hood exhaust fans.
8.10.6 Chemical fume hoods equipped with control systems that vary the hood exhaust
airflow as the sash opening varies and/or in conjunction with whether the laboratory
room is in use (occupied/unoccupied) shall be equipped with a user accessible means
to attain maximum hood exhaust airflow regardless of sash position when necessary or
desirable to ensure containment and removal of a potential hazard within the hood.
(Continued on Next Page)
The requirement that a user be able to apply
maximum exhaust to a fume hood regardless of
sash position primarily pertains to fume hoods
with VAV control systems that decrease fume
hood exhaust to maintain a constant face
velocity as the sash opening decreases. It is
conceivable that even with a sash fully closed
(and the exhaust thus minimized) a fire or highly
active chemical reaction may warrant
maximizing the fume hood exhaust without
having to open the sash. This capability is
normally implemented by including an
appropriate emergency exhaust activation
pushbutton on the fume hood’s monitoring
device.