Basic Documentation
Table Of Contents
- Introduction
- Applicable Definitions (Alphabetical Listing)
- Laboratory Safety
- Hazard Assessment
- Chemical Hygiene Plan
- Chemical Hygiene Responsibilities
- Fume Hoods
- When Required & Safe Usage
- Gloveboxes:
- Face Velocity
- Face Velocity Setback
- Size & ADA Compliance
- CAV (Constant Air Volume) Bypass
- CAV (Constant Air Volume) Conventional
- VAV (Variable Air Volume)
- VAV Diversity
- Automatic Sash Closure
- Safe Operation of Sashes
- Accessories, Services and Explosion Protection
- Ductless
- Auxiliary Air
- (Special Purpose) Perchloric Acid
- Room Air Cross Currents
- Minimum Exhaust
- Monitoring
- Selection Criteria and Performance Specifications
- Laboratory Design & Fume Hood Implementation
- Maintenance
- Periodic Testing
- Test Procedures
- Signage and Recordkeeping
- Shutdown Procedures
- Evaluating CAV (Constant Air Volume) Systems
- Evaluating VAV (Variable Air Volume) Systems
- Biological Laboratories
- Biosafety Level 1
- Biosafety Level 2
- Biosafety Level 3
- Biosafety Level 4
- Ventilation for Biosafety Level 1
- Ventilation for Biosafety Level 2
- Ventilation for Biosafety Level 3
- Ventilation for Biosafety Level 4, Cabinet Laboratory
- Ventilation for Biosafety Level 4, Suit Laboratory
- Containment Levels - Canada
- Containment Levels and Ventilation Requirements: Canada
- Biological Safety Cabinets and Classifications
- Biosafety Cabinet Applications
- Biosafety Cabinets – Installation and Safe Usage Recommendations
- Biosafety Cabinets – Certification and Safe Usage - Canada
- Biological Safety Cabinet Design, Construction and Performance Requirements
- Biosafety Cabinet Testing
- Ventilation Systems
- Local Ventilation -When Required
- Ventilation Rates for Animal Rooms
- Ventilation Rates for Animal Rooms
- Ventilation Rates for Biological Labs
- Ventilation Rates for Chemical Laboratories
- Ventilation rates for Storage areas
- Room Supply Air
- Supply Air Quality and Filtration
- Room and Duct Pressurization
- Human Occupancy, Room Temperature and Humidity
- Animal Rooms Room Temperature and Humidity
- Load Calculations
- Room Sound Level and Vibration
- Emergency Control Provisions
- Energy Conservation
- Monitoring
- Maintenance
- Periodic Inspection and Testing
- Periodic Inspection and Testing - Canada
- Test Records
- Management
- Exhaust Systems
- Configuration
- Leakage
- Components
- Manifolded Systems
- Air Velocity
- Stack Height and Discharge Location
- Operational Reliability
- Recirculated Air and Cross Contamination
- Materials and Fire Protection
- Commissioning
- Commissioning - Canada
- Referenced Publications
Laboratory Ventilation Codes and Standards
Siemens Industry, Inc. 70
Topic
Requirement(s)
Commentary
Containment
Levels -
Canada
Public Health Agency of Canada, Office of Laboratory Security, Biosafety
Division, Laboratory Biosafety Guidelines, 3
rd
Edition 2011:
Containment level 1 (CL1)
CL1 requires no special design features beyond those suitable for a well-designed
and functional laboratory. Biological safety cabinets (BSC’s) are not required. Work
may be done on an open bench top, and containment is achieved through the use of
practices normally employed in a basic microbiology laboratory.
Containment level 2 (CL2)
The primary exposure hazards associated with organisms requiring CL2 are through
the ingestion, inoculation and mucous membrane route. Agents requiring CL2
facilities are not generally transmitted by airborne routes, but care must be taken to
avoid the generation of aerosols (aerosols can settle on bench tops and become an
ingestion hazard through contamination of the hands) or splashes. Primary
containment devices such as BSC's and centrifuges with sealed rotors or safety cups
are to be used as well as appropriate personal protective equipment (that is, gloves,
laboratory coats, protective eyewear). As well, environmental contamination must be
minimized by the use of handwashing sinks and decontamination facilities
(autoclaves).
Containment Level 3 (CL3)
These agents may be transmitted by the airborne route, often have a low infectious
dose to produce effects and can cause serious or life-threatening disease. CL3
emphasizes additional primary and secondary barriers to minimize the release of
infectious organisms into the immediate laboratory and the environment. Additional
features to prevent transmission of CL3 organisms are appropriate respiratory
protection, HEPA filtration of exhausted laboratory air and strictly controlled
laboratory access.
Containment Level 4 (CL4)
These agents have the potential for aerosol transmission, often have a low infectious
dose and produce very serious and often fatal disease; there is generally no
treatment or vaccine available. This level of containment represents an isolated unit,
functionally and, when necessary, structurally independent of other areas. CL4
emphasizes maximum containment of the infectious agent by complete sealing of the
facility perimeter with confirmation by pressure decay testing; isolation of the
researcher from the pathogen by his or her containment in a positive pressure suit or
containment of the pathogen in a Class III BSC line; and decontamination of air and
other effluents produced in the facility.
(Continued on Next Page)