Commissioning Instructions

Before You Begin
Setting Controller Address
4 | 11
Siemens Industry, Inc.
Restricted
Setting Controller Address
1.
If using the sensor bus to communicate the face area:
Verify CTLR ADDRESS is correct (default is 51 and does not need to be
changed).
Setting the Application
1.
Select the desired application.
2950 Slave Mode
2951 Bench style fume hoods 4 independent vertical sashes
2952 Floor Mounted style fume hoods 2 independent sets of 2
vertical sashes, one on top of the other
2953 Dual Floor Mounted style fume hoods 4 independent sets of 2
vertical sashes, one on top of the other
2954 Bench style fume hoods 2 to 10 horizontal sashes
2955 Bench style fume hoods 1 vertical carrier with 2 to 9 horizontal
sashes
2956 Floor Mounted style fume hoods 2 vertical sashes, with top
sash having 2 to 8 horizontal sashes
2957 Dual Bench style fume hoods 2 vertical carries (non-
overlapping) each with 2 to 4 horizontal sashes in the vertical carrier
2958 Floor Mounted style fume hoods 2 vertical sashes
(overlapping), with each sash having 2 to 4 horizontal sashes
Setting Units
NOTE:
All measurements entered during the start-up sequences can either be English or
SI values (listed in parentheses after the English unit), depending on which unit
type is selected, using the
Metric/English Units button, in the appropriate tool.
Fume Hood Specific Sash Setup and Calibration
This section presents the steps for calibrating the Fume Hood Sash Open Area
Module sash sensors and configuring the face area parameters.
Sash Setup and Calibration
NOTE:
Enter all measurements to the nearest .0.25 inch (0.635 cm).