Commissioning Instructions
Before You Begin
Fume Hood Specific Sash Setup and Calibration
7 | 11
Siemens Industry, Inc.
A6V10801615
Restricted
07.06.2016
Example Combination Sash Fume Hood with Fixed Area.
Sash Calibration
NOTE:
The full travel of the sash must be used during calibration.
NOTE:
It is recommended that the vertical sash be calibrated before the horizontal
sashes.
1.
Set CAL SASH NUM to 1.
2.
Verify CAL SASH LOC is set to MIN.
3.
Slide vertical sash 1 to the closed position. Measure the distance from the
bottom of vertical sash 1 to the bottom of the sash opening in inches (cm).
Set CAL SASH POS to this value. When the SOAM accepts the reading,
CAL SASH POS will revert back to
257 and CAL SASH LOC will switch to
MAX.
4.
Verify CAL SASH LOC is set to MAX.
5.
Slide vertical sash 1 to the full open position. Measure the distance from the
bottom of vertical sash 1 to the bottom of the sash opening in inches (cm).
Set CAL SASH POS to this value. When the SOAM accepts the reading, the
maximum position value will be automatically entered into POS SASH 1 and
CAL SASH POS will revert back to
257, CAL SASH LOC will switch to MIN,
and CAL SASH NUM will return to
0.
6.
Verify CAL SASH LOC is set to MIN.
7.
Slide the sash panel to be calibrated to the far left. Measure the distance
from the left end of the track to the left edge of the sash panel. Set CAL
SASH POS to this value. When the sash aggregator accepts the reading,
the minimum position value will be entered into POS SASH 2.