3. Use the alcohol towelette to clean the surface on
which the UniTrak is to be applied. Dry the
surface thoroughly before mounting the UniTrak.
4. Measure and mark with the pencil the midpoint
of the fume-hood mounting surface. Measure
and mark with the pencil the midpoint of the
UniTrak sensor.
5. Remove the protective backing from the UniTrak
sensor.
6. Align the two marks made in Step 4. When
attaching the UniTrak to the mounting surface
hold one end up and lightly place the opposite
end down. The UniTrak must be mounted as
straight as possible.
NOTE: If applied without pressure to the
mounting surface, you may remove
and reapply the UniTrak if
necessary. If pressure is applied, the
adhesive is permanent.
Bending Linkage (Vertical)
NOTE: Bends will reduce overall length by 1/2
inch to 1-1/2 inches.
Outside sash UniTrak mount
1. Estimate the mounting position of the linkage
(approximately 1 inch from the edge of the sash)
(Figure 9).
FUM0346R1
Figure 9. Location of Vertical Linkage.
FUM0217R2
SASH
HANDLE
X
ACTUATOR
BLOCK
UNITRAK
VERTICAL
SASH LINKAGE
FUM0359R1
Figure 10. Measuring Between Sash and
UniTrak Sensor.
2. Measure the distance from the edge of the sash
frame to the far edge of the actuator block = X
(Figure 10).
3. Add 1-1/2 inches to X.
4. Using the 1-1/2 inches + X value, measure from
the outer edge of the mounting plate and mark
this location (Figure 11).
(X+1 1/2")
MARK LINKAGE
AND BEND HERE
Figure 11. Marking First Linkage Bend.
Page 6 of 13 Siemens Building Technologies, Inc.