Application

Point Database Application 2942
36
Siemens Industry, Inc. Application Note, Apps 2941/2942 140-1319
Restricted 2015-11-04
Point
Number
a),
b)
Descriptor
Factory
Default
(SI Units)
c)
Eng Units
(SI Units)
c)
Slope
(SI Units)
c)
Intercept
(SI Units)
c)
On Text
Off Text
66 VERT WIDTH2 0.0 (0.0) INCHES
(CM)
0.5 (1.27) 0 -- --
67 VSASH HGHT1 0.0 (0.0) INCHES
(CM)
0.5 (1.27) 0 -- --
68 VSASH HGHT2 0.0 (0.0) INCHES
(CM)
0.5 (1.27) 0 -- --
69 TRACK HEIGHT 0.0 (0.0) INCHES
(CM)
0.5 (1.27) 0 -- --
70 BYPASS HGHT 0.0 (0.0) INCHES
(CM)
0.5 (1.27) 0 -- --
{71} BYPASS OPEN 100 PCT 1 0 -- --
72 FAIL AREA 0.0 (0.0) SQ. FT
(SQ M)
0.003472222
(0.00032258)
0 -- --
{73} EXTERNAL A 0.0 (0.0) SQ. FT
(SQ M)
0.003472222
(0.00032258)
0 -- --
74 MAX EXT AREA 0.0 (0.0) SQ. FT
(SQ M)
0.003472222
(0.00032258)
0 -- --
75 MIN EXTVOLTS 1 VOLTS 0.01 0 -- --
{78} CAL EXH VLV NO -- -- -- YES NO
79 EXH VLV STAT NOTCAL -- -- -- NOTCAL CAL OK
{80} EXH MAX 3500
(1651.65)
CFM ( LPS) 4 (1.8876) 0 -- --
{81} EXH MIN 192
(90.6048)
CFM ( LPS) 4 (1.8876) 0 -- --
{82} EXH STPT 0 (0.0) CFM ( LPS) 4 (1.8876) 0 -- --
{83} FVEL STPT 100 (0.508) FPM (
MPS)
1 (0.00508) 0 -- --
84 OCC FV STPT 100 (0.508) FPM (
MPS)
1 (0.00508) 0 -- --
85 UNOC FV STPT 90 (0.4572) FPM (
MPS)
1 (0.00508) 0 -- --
86 OCC LOW FV 100 (0.508) FPM (
MPS)
1 (0.00508) 0 -- --
87 OCC HIGH FV 100 (0.508) FPM (
MPS)
1 (0.00508) 0 -- --
88 OCC DELAY 30 SEC 1 0 -- --
{89} EXH SIG AO2 0 VOLTS 0.01 0 -- --
90 AO2 RANGE 0 (0.0) CFM ( LPS) 4 (1.8876) 0 -- --
91 AO2 DEADBAND 5.2 PCT 0.4 0 -- --
92 AO2 V MIN 1 VOLTS 0.01 0 -- --
{94} CAL AIR NO -- -- -- YES NO
95 CAL SETUP 4 -- 1 0 -- --