Commissioning Instructions
Before You Begin
Flashing Controller Firmware
10 | 11
Siemens Industry, Inc.
A6V10801617
Restricted
07.06.2016
AO DEADBAND defaults to 0%. If FACE A OUT changes by less than the
percentage value in AO DEADBAND, the output will not update. Once the value
changes greater than the AO DEADBAND, the output will be updated to the
currently calculated value.
If needed, set MIN FA VOLTS (default = 1 Vdc).
MIN FA VOLTS can be left at default for most installations. Changing this value
changes the voltage output when the FACE AREA = 0 sq ft.
NOTE:
If the MIN FA VOLTS is set to 0, failure detection is lost.
Flashing Controller Firmware
WCIS Procedure
1. Connect to the USB port of the SOAM.
2. From the Device menu, select Load TEC Firmware.
The Load TEC Firmware dialog box displays.
3. Click the Browse button.
4. Browse to the folder where the new firmware is saved.
5. Double-click the firmware file and then click Load.