Description
The Lab Room Exhaust Air Terminal consists of the
following components:
Round duct casing, damper blade, and airflow
sensor in sizes from 4 inches to 18 inches
diameter.
Material offerings: Galvanized steel, 316L
stainless steel, Teflon-coated cold-rolled steel.
(Optional) Galvanized steel equipment enclosure
with exterior supply connection.
(Optional) Factory-mounted controls.
Specifications
Materials (within air stream) Standard
Construction
A
Construction
B
Construction
C
Damper Shaft
Flanges
Materials (outside air stream) Standard
Control Enclosure
Pneumatic Tubing
Pneumatic Fittings
with enclosure only
Airflow Measurement
Sensor Type A
Square edge orifice plate.
One set of averaging pressure taps.
Same material as duct casing.
Sensor Type B
Four quadrants, with 12 sensing
points, center averaging and signal
amplification.
One set of averaging pressure taps.
Accuracy
Flow Measurement
±3% of actual flow @ listed ranges
(Sensor only, per AMCA 610.)
Installation
Requirements
Rigid duct of the same diameter 1 x
duct diameters upstream from the
sensor, or taper angle less than 30
degrees.
Airflow Control
Damper Blade
Round single blade with 90 degree
control.
Environmental
Operating
Temperature/% RH
40 to 120°F (4 to 50°C)
0 to 95% non-condensing
Storage
Temperature/% RH
-10 to 150°F (-23 to 65°C)
0 to 95% non-condensing
Dimensions
Sizes
See Figure 2 and Figure 3
Weight
20 to 32 lbs. (9.1 to 14.5 kg)