Operating Instructions
Chapter 3 – Point Database
16
Siemens Industry, Inc.
Owner's Manual
125-5111
2015-06-30
Descriptor
Address
1
Application
Description
SUPDUCT AREA
97
2931, 2997
Area, in square feet (square meters), of the duct where the
air velocity sensor is located. This value is calculated by the
field panel depending on duct shape and size. It is used in
calculating all points in units of cfm, CF, lps, and L.
LOOP TIME
98
2931
The time, in seconds, between control loop calculations.
ERROR STATUS
{99}
2931, 2997
The status code indicating any errors detected during
controller power up. A status of 0 indicates there are no
problems.
REHEAT CLOSD
102
2931
The value of REHEAT AO1 that closes the reheat valve
completely.
REHEAT OPEN
103
2931
The value of REHEAT AO1 that opens the reheat valve
completely.
STAT SUPV
{104}
2931, 2997
Room unit configuration point, values are additive.
PRESS D GAIN
105
2931
Differential feedback gain used to tune the room pressure
control.
MODHTG FLO
106
2931
The minimum flow in feet per minute needed for safety
purposes when using electric reheat.
DO DIR.REV
107
2931, 2997
Reverses the output state for selected non-motor digital
outputs.
RM RH
{108}
2931, 2997
Room humidity when room unit is provided with humidity
sensing.
FAIL TIME
109
2931
Indicates when the air volume is too far away from setpoint
for too long.
PRES ALM DEL
110
2931
Delay period that prevents “nuisance alarms” on the room
pressure control alarm.
SUP DMP POS
{111}
2931
The current position of the supply damper motor in percent of
full travel. This value is calculated based on motor run time.
MTR1 TIMING
112
2931
The time required for the Motor 1 actuator to travel from full
closed to the full open position.
MTR1 ROT ANG
113
2931
The angle that Motor 1 rotates from fully closed to fully open.
GEX DMP POS
{114}
2931
The current position of the exhaust damper motor in percent
of full travel. This value is calculated based on motor run
time.
MTR2 TIMING
115
2931
The time required for the Motor 2 actuator to travel from full
closed to the full open position.
MTR2 ROT ANG
116
2931
The angle that Motor 2 rotates from fully closed to fully open.
MTR3 TIMING
117
2931
The status code indicating any errors detected during
controller power up. A status of 0 indicates there are no
problems.
RM CO2
{118}
2931, 2997
A point can be unbundled in the controller for monitoring
purposes. This point may be used in a control strategy as
occupancy increases (CO2 levels increase) in the room
being controlled.
REHEAT POS
{119}
2931
The current position of the reheat valve in percent of full
travel. This value is calculated based on motor run time.
SUP DMP CLOS
120
2931
The value of SUP DMP AO2 that closes the damper all the
way.