Operating Instructions

Chapter 3 Point Database
17
Siemens Industry, Inc.
Owner's Manual
Descriptor
Address
1
Application
Description
SUP DMP OPEN
121
2931
The value of SUP DMP AO2 that open the damper all the
way.
GEX DMP CLOS
122
2931
The value of GEX DMP AO3 that closes the damper all the
way.
GEX DMP OPEN
123
2931
The value of GEX DMP AO3 that open the damper all the
way.
NO PR VOL DF
125
2931
The value in CFM that the room is controlled to if the room
pressure sensor fails.
PPCL STATE
{127}
2931, 2997
An indicator that customized programming has been added
in addition to the normal control strategy of the application
being used. This point is read as LOADED or EMPTY. A
status of LOADED indicates that there is PPCL programming
in the controller, and it is providing unique control to meet a
customer's job specification. A status of EMPTY indicates
that no unique programming is present.
1)
Points not listed are not used in this application.
2)
Point numbers that appear in brackets { } may be unbundled at the field panel.