Application

Sequence of Operation
BTU Calculations
21
Siemens Industry, Inc.
Application Note, App 2927
Temperature Control Sequence.
BTU Calculations Constant Volume Mode
During the Constant Volume Mode, the BTU Compensator operates as follows:
During Constant Volume operation, the controller adjusts the supply air temperature
set point as necessary to maintain CTL TEMP at CTL STPT. The room temperature
PID loop calculates the value of TEMP LOOPOUT. This value is used to adjust the
value of the supply air temperature set point. The loop is tuned by adjusting the values
of the feedback gain points, ROOM P GAIN and ROOM I GAIN and the sample interval
point, LOOP TIME.
The output of the room temperature loop, TEMP LOOPOUT, reflects the load
requirements. The value of TEMP LOOPOUT is a supply air temperature expressed as
“degrees above or below the room temperature set point if the supply flow is at 100%”.
If the supply flow is less than 100% of the currently active air supply airflow maximum,
DISCH STPT is adjusted to an amount greater than TEMP LOOPOUT by a
corresponding percentage.
Example
CTL STPT = 70°F: OCC.UNOCC = OCC
If
TEMP LOOPOUT =
and
SUP AIR VOL =
then
DISCH STPT =
Formula for DISCH STPT:
CTL STPT +
(TEMP LOOPOUT x
100% ÷ SUP AIR VOL)
10°F
OCC SUP MAX
80°F
70° + (10° x 100% ÷ 100%)
10°F
0.5 ´ OCC SUP MAX
90°F
70° + (10° x 100% ÷ 50%)
–5°F
0.25 ´ OCC SUP MAX
50°F
70° + (–5° x 100% ÷ 25%)
0°F
any flow
70°F
70° + (0° x 100% ÷ x%)