Application
Sequence of Operation
Fail Mode Operation
26
Siemens Industry, Inc.
Application Note, App 2927
140-1311
2015-07-07
The last two values of AVS FAILMODE do not describe specific actions; that is, when
an AVS fails, the supply and general exhaust will react differently depending on the
circumstances.
If AVS FAILMODE equals
7, the supply Damper will hold. The general exhaust
Damper will also hold if a fume hood is present (that is, if MAX HOOD VOL > 0). If a
fume hood is absent, then the general exhaust Damper will close if the room is being
positively pressurized and open if the room is neutral or negatively pressurized (that is
if VOL DIF STPT is equal to or greater than 0).
If AVS FAILMODE equals
8, the supply Damper will open if the room is being positively
pressurized and close if the room is neutral or negatively pressurized. The general
exhaust Damperwill hold if a fume hood is present. If a fume hood is absent, the
general exhaust Damper will close if the room is being positively pressurized and open
if the room is neutral or negatively pressurized.
NOTE:
If AVS FAILMODE is set greater than 8, it will default to 0.
Fail Mode Operation
If one of the controller’s accessories (inputs) fails, a failure mode sequence is initiated
that leads to the failure of VOL DIFFRNC. The following figure shows the order in
which points will fail.
* If MAX HOOD VOL is set to 0, a “Failed” status of HOOD VOL will not initiate a failure
in TOTL EXHAUST or VOL DIFFRNC. See
Fume Hood Flow Input
.
Air Velocity Sensors – If one or both of the LCM air sensor signals (SUP AIR VOL,
GEX AIR VOL) are out of range (for example, improper wiring to/from the Offboard Air
Module(s), tubing not connected or connected backward), then the actions of the
supply and general exhaust Dampers will depend on the value of AVS FAILMODE.
Once GEX AIR VOL and SUP AIR VOL are normal, the supply and general exhaust
Dampers return to normal operation.
See
Operation of AVS FAILMODE
for more information.