Application

Point Database Application 2927
31
Siemens Industry, Inc.
Application Note, App 2927
Point Database Application 2927
Point
Number
Descriptor
Factory
Default (SI
Units)
Eng Units
(SI Units)
Slope
(SI Units)
Intercept
(SI Units)
On Text
Off Text
1
CTLR ADDRESS
99
--
1
0
--
--
2
APPLICATION
2997
--
1
0
--
--
3
TEMP OFFSET
0.0 (0.0)
DEG F
(DEG C)
0.25 (0.14)
-31.75(-17.78)
--
--
{04}
ROOM TEMP
74.0
(23.44888)
DEG F
(DEG C)
0.25 (0.14)
48.0 (8.88888)
--
--
5
OCC DIF STPT
400
(188.7599)
CFM (LPS)
4 (1.8876)
-8000 (-3775.2)
--
--
6
UOC DIF STPT
400
(188.7599)
CFM (LPS)
4 (1.8876)
-8000 (-3775.2)
--
--
7
RM STPT MIN
55.0
(12.80888)
DEG F
(DEG C)
0.25 (0.14)
48.0 (8.88888)
--
--
8
RM STPT MAX
90.0
(32.40888)
DEG F
(DEG C)
0.25 (0.14)
48.0 (8.88888)
--
--
{09}
TEMP CTL VOL
0 (0.0)
CFM (LPS)
4 (1.8876)
0
--
--
10
GEX DMPR DIR
NOPEN
--
--
--
NCLOSE
NOPEN
11
SUP DMPR DIR
NCLOSE
--
--
--
NCLOSE
NOPEN
12
OCC ENA
0
--
1
0
--
--
{13}
ROOM STPT
74.0
(23.44888)
DEG F
(DEG C)
0.25 (0.14)
48.0 (8.88888)
--
--
{14}
AI 4
0
PCT
0.1
0
--
--
{15}
HOOD SIG AI3
0
VOLTS
0.01
0
--
--
16
VENT ALM DEL
30
SEC
1
0
--
--
17
ALARM ENA
0
--
1
0
--
--
{19}
OCC BUTTON
OFF
--
--
--
ON
OFF
{21}
OCC.UNOCC
OCC
--
--
--
UNOCC
OCC
{22}
VOL DIF ALM
OFF
--
--
--
ON
OFF
{23}
NET ALM CMD
OFF
--
--
--
ON
OFF
{24}
OCC SWIT DI2
OFF
--
--
--
ON
OFF
{25}
BUTTON CMD
OCC
--
--
--
UNOCC
OCC
26
GEX P GAIN
0.04
--
0.001
0
--
--
{27}
ALM SWIT DI6
OFF
--
--
--
ON
OFF
28
TRACK MODE
0
--
1
0
--
--
{29}
NET OCC CMD
OCC
--
--
--
UNOCC
OCC
{30}
GEX AIR VOL
0 (0.0)
CFM (LPS)
4 (1.8876)
0
--
--