Application

Point Database Application 2927
32
Siemens Industry, Inc.
Application Note, App 2927
Point
Number
Descriptor
Factory
Default (SI
Units)
Eng Units
(SI Units)
Slope
(SI Units)
Intercept
(SI Units)
On Text
Off Text
{31}
OCC SUP MAX
3400
(1604.46)
CFM (LPS)
4 (1.8876)
0
--
--
{32}
OCC SUP MIN
340
(160.446)
CFM (LPS)
4 (1.8876)
0
--
--
{33}
OCC GEX MAX
1100
(519.09)
CFM (LPS)
4 (1.8876)
0
--
--
{34}
OCC GEX MIN
600
(283.14)
CFM (LPS)
4 (1.8876)
0
--
--
{35}
SUP AIR VOL
0 (0.0)
CFM (LPS)
4 (1.8876)
0
--
--
36
SUP FLO COEF
0.73
--
0.01
0
--
--
{37}
REHEAT AO1
0
VOLTS
0.01
0
--
--
38
DIF ALM DBD
100 (47.19)
CFM (LPS)
4 (1.8876)
0
--
--
39
DIF ALM DEL
30
SEC
1
0
--
--
40
AVS FAILMODE
0
--
1
0
--
--
{41}
SUP EXTN DO1
HOLD
--
--
--
EXTN
HOLD
{42}
SUP RETC DO2
RETC
--
--
--
HOLD
RETC
{43}
GEX EXTN DO3
HOLD
--
--
--
EXTN
HOLD
{44}
GEX RETC DO4
RETC
--
--
--
HOLD
RETC
45
TRACK METHOD
FLOW
--
--
--
FLOW
STPT
{46}
DO 5
OFF
--
--
--
ON
OFF
{47}
ALARM DO7
OFF
--
--
--
ON
OFF
{48}
AUTOZERO DO8
OFF
--
--
--
ON
OFF
{49}
VALVE CMD
0
PCT
0.4
0
--
--
{50}
GEX DMPR CMD
-100
--
1
-100
--
--
51
DISCH MIN
55.0
(12.856)
DEG F
(DEG C)
0.5 (0.28)
37.5(3.056)
--
--
52
MAX HOOD VOL
0 (0.0)
CFM (LPS)
4 (1.8876)
0
--
--
{53}
TOTL EXHAUST
0 (0.0)
CFM (LPS)
4 (1.8876)
0
--
--
54
GEX FLO COEF
0.73
--
0.01
0
--
--
{55}
AO2
0
VOLTS
0.01
0
--
--
{56}
AO3
0
VOLTS
0.01
0
--
--
57
VALVE CLOSED
10
VOLTS
0.01
0
--
--
58
VALVE OPEN
0
VOLTS
0.01
0
--
--
59
DISCH MAX
120.0
(49.256)
DEG F
(DEG C)
0.5 (0.28)
37.5(3.056)
--
--
60
GEXDUCT AREA
1.0
(0.09292)
SQ. FT (SQ
M)
0.025
(0.002323)
0
--
--
{61}
OTHER SUP
0 (0.0)
CFM (LPS)
4 (1.8876)
0
--
--
{62}
SUP DMPR CMD
-100
--
1
-100
--
--